12 ProcessLogix Controller
Publication 1757-IN901D-EN-P - May 2007
Specifications
ProcessLogix Controller - 1757-PLX52
Attribute Value
Intrinsically safe No
Temp. rate of change ≤ 1 °C/min (≤ 33.8 °F/min)
Corrosives G2 std, G3 option (ISA S71.04)
Emissions CISPR 11:
Group 1, Class A
ESD immunity IEC 61000-4-2:
4 kV indirect contact discharges
Radiated RF immunity IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80%AM from 80…2000 MHz
Power requirements 24V dc @ 5 mA
5.1V dc @ 1.6 A
3.3V dc @ 1.3 A
1.2V dc @ 7 mA
Controller battery backup time
Lithium battery
(standard, built in)
144 hours (non-rechargeable) - 6 days:
Replacement Battery: 1757-PLXBAT
Lithium battery is disconnected during shipment.
Battery Extension Module,
1757-BEM
120 hours (rechargeable) - 5 days
Spare Battery: 1757-BEMS
Removal/Insertion under power
(RIUP)
Permitted when equipment is installed in ordinary, non-hazardous,
locations (I/O modules reload automatically).
Not permitted when equipment is installed in a Class I, Division 2,
Hazardous (Classified) Location.