Rockwell-automation 1757-FFLDC4 ControlNet Foundation Fieldbus Linking Uživatelský manuál Strana 7

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 32
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 6
ControlNet Foundation Fieldbus Linking Device 7
Publication
1757-IN022B-EN-P - August 2009
Before You Begin
Before you install the linking device, read and complete the following
sections.
Software Requirements
The following software is compatible with this revision of the linking device:
RSFieldbus software, version 2.03 or later
RSLinx Classic software, version 2.52 or later
RSNetWorx for ControlNet software, version 8.00 or later
Logix5000 Clock Update tool
RSLogix 5000 programming software, version 16.03 or later
WARNING
This product contains a ControlNet daughtercard (CAM) that is not intended for
removal. Any attempt to remove this CAM or to operate the CAM release
mechanism may cause irreparable damage. If you insert or remove the CAM
while host power is on, an electrical arc can occur. This could cause an
explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.
IMPORTANT
You must upgrade your linking device to RSLogix 5000 programming
software version 17 to program unscheduled Class 1 connections on the
ControlNet network. The upgrade is required if your system is running
RSLogix 5000 software version 16 without redundancy. If you are using
RSLogix 5000 software version 16 with redundancy, unscheduled Class 1
connections are not available on the ControlNet network.
Zobrazit stránku 6
1 2 3 4 5 6 7 8 9 10 11 12 ... 31 32

Komentáře k této Příručce

Žádné komentáře