ControlNet Foundation Fieldbus Linking Device 19
Publication
1757-IN022B-EN-P - August 2009
Reset Configuration
The Reset Configuration deletes all downloaded fieldbus configurations. The
linking device retains its Ethernet network configuration and web page
password information through this reset. To reset the configuration, complete
the following steps.
1. Remove power from the linking device.
2. Move the jumper from its original position (two right pins) to the two
left pins.
3. Wait 30 seconds.
4. Move jumper back to its original position.
5. Return power to the linking device.
Reset/delete
function blocks
This deletes all blocks
in the linking device
except for the
Resource Block. All
Resource Block
parameters are reset
to factory default,
including the tag
name.
RSFieldbus
Resource
Block,
Factory
parameter
(remotely)
RSFieldbus User Manual,
publication RSFBUS-UM001
IMPORTANT
After you complete any type of reset, verify that the time and time zone are
still correct.
WARNING
When you insert or remove the jumper while power is on, an electrical arc can
occur. This could cause an explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.
Linking Device Reset Types