Rockwell-automation 1756-IH16ISOE ControlLogix Sequence of Events Modu Uživatelský manuál Strana 116

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 160
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 115
Publication 1756-UM528A-EN-P - April 2004
A-6 Specifications and Module Block Diagrams
Conductors
Wire Size
Category
#22 to #14 AWG (0.324 to 2.08 sq. mm) stranded
(1)
3/64 inch (1.2mm) insulation maximum
1
(2)
Screwdriver Blade Width for
RTB
1/8 inch (3.2mm) maximum
Environmental Conditions
Operational
Temperature
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0 to 60°C (32 to 140°F)
Storage Temperature IEC 60068-2-1 (Test Ab, Un-packaged Non-operating
Cold),
IEC 60068-2-2 (Test Bb, Un-packaged Non-operating
Dry Heat),
IEC 60068-2-14 (Test Na, Un-packaged
Non-operating Thermal Shock):
-40 to 85°C (-40 to 185°F)
Relative Humidity IEC 60068-2-30 (Test Db, Un-packaged
Non-operating Damp Heat):
5 to 95% non-condensing
Vibration IEC 60068-2-6 (Test Fc, Operating):
2g @ 10-500Hz
Operating Shock IEC 60068-2-27 (Test Ea, Unpackaged Shock):
30g
Non-operating Shock IEC 60068-2-27 (Test Ea, Unpackaged Shock):
50g
Emissions CISPR 11:
Group 1, Class A
ESD Immunity IEC 61000-4-2:
6kV contact discharges
8kV air discharges
Radiated RF Immunity IEC 61000-4-3:
10V/m with 1kHz sine-wave 80%AM from 80MHz to
1000MHz
10V/m with 200Hz 50% Pulse 100%AM at 900Mhz
10V/m with 200Hz 50% Pulse 100%AM at 1890Mhz
Zobrazit stránku 115
1 2 ... 111 112 113 114 115 116 117 118 119 120 121 ... 159 160

Komentáře k této Příručce

Žádné komentáře