GuardPLC Digital Output Module 13
Rockwell Automation Publication 1753-IN005B-EN-P - June 2010
EFT/B Immunity
• IEC 61000-4-4
• ±2 kV @ 5 kHz on DC power ports
• ±1 kV @ 5 kHz on signal ports
• ±1 kV @ 5 kHz on communication ports
Surge Transient Immunity
• IEC 61000-4-5
• ±500V line-line (DM) and ±500V line-earth (CM)
on DC power ports
• ±1 kV line-earth (CM) on signal ports
• ±1 kV line-earth (CM) on communication ports
Conducted RF Immunity
• IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from
150 kHz…80 MHz
Damped Oscillatory Wave Immunity
• IEC 61000-4-12
• ±1 kV line-earth (CM) on signal ports
• ±1 kV line-earth (CM) on power ports
Certifications
Certification (when
product is marked)
(1)
(1) See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification
details.
1753-IB16
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File
E65584.
CE European Union 2004/108/EC EMC Directive, compliant with:
• EN 61326-1 Meas./Control/Lab., Industrial Requirements
• EN 61000-6.2; Industrial Immunity
• EN 61000-6-4; Industrial Emissions
• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11;
Industrial Emissions
Functional Safety Certified by TÜV
(2)
: up to and including SIL 3 according to IEC 61508 and PLe
(Cat. 4) according to ISO 13849-1
(2) When used with specified firmware revisions.
Environmental Specifications – 1753-OB16 Module