Publication 1747-UM002A-US-P - June 2000
6-66 Library of Routines
OC_SetupPowerFail
Action
OC_SetupPowerFailAction registers the action to be taken when a
power fail interrupt is received from the scanner.
Syntax:
int OC_SetupPowerFailAction(HANDLE handle,
BYTE *bufptr, WORD offset, WORD length, void
(*callback)() );
Parameters:
Description:
You can configure the power failure action in four ways:
• No action (default); the power failure interrupt is ignored
(bufptr is NULL; callback is NULL)
• Copy a block of data to the host retentive data partition in dual
port RAM (bufptr points to the data to save; callback is
NULL)
• Execute a user callback function (bufptr is NULL; callback
points to the routine to call)
• Copy a block of data and execute a callback function (bufptr
points to the data to save; callback points to the routine to
call)
Parameter: Description:
handle Must be a valid handle returned from OC_OpenScanner
bufptr If
bufptr is:
NULL no data is copied (default)
Not NULL at power fail
length bytes of data are copied
from
bufptr to the host retentive data partition
starting at
offset.
offset Specifies the offset within the host retentive data partition to begin
copying
length Number of bytes to copy
If
length points beyond the end of the host retentive data partition,
it is truncated
callback If
callback is:
NULL no callback function is executed (default)
Not NULL the power fail interrupt routine calls this function
after copying the data to the host retentive data
partition (if configured)