Publication 1747-UM002A-US-P - June 2000
Library of Routines 6-47
Return Value:
Considerations:
Supported in the DOS API library and the Windows NT API library
Example:
HANDLE Handle;
BYTE retent_data[500];
int retcode;
retcode = OC_ReadHostRetentiveData( Handle, retent_data,
0, 500 );
OC_ReadInputImage
OC_ReadInputImage reads the current input image from the scanner.
Syntax:
int OC_ReadInputImage(HANDLE handle,
WORD *inpimgcpy, int slotnum, WORD offset,
WORD len, WORD *imagebuf);
Parameters:
Name: Value: Description:
SUCCESS 0 host retentive data was written successfully
ERR_OCACCESS 2
handle does not have access to scanner
ERR_OCINIT 5 scanner has not been initialized, see OC_InitScanner
ERR_OCPARAM 8 parameter contains invalid value
Parameter: Description:
handle Must be a valid handle returned from OC_OpenScanner
inpimgcpy If
inpimgcpy
is:
NULL OC_ReadInputImage reads data directly from
the input image in the scanner’s shared
memory.
not NULL OC_ReadInputImage reads data from
inpimgcpy which contains a copy of the
scanner’s input image.
slotnum
offset
len
If
slotnum is:
positive input data for that slot is read into the array
pointed to by
imagebuf. Then imagebuf
contains len words of input data starting at
word
offset of the module in the slot. Data
will not be read past the end of the input image
for the slot.
-1 the entire input image is read into the array
pointed to by
imagebuf
,
and offset and
len are ignored.
imagebuf Must point to an array that is large enough to accept the amount of
data in the requested input image