Rockwell-automation 1738-SSIM23 ArmorPoint I/O SSI Absolute Encoder Mo Uživatelský manuál Strana 10

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 14
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 9
Publication 1738-IN013A-EN-E - June 2004
10 ArmorPoint I/O Synchronous Serial Interface (SSI) Absolute Encoder Module, Series A
Indication Probable Cause
Network Status
Off Device is not on line:
- Device has not completed dup_MAC-id test.
- Device not powered - check module status indicator.
Flashing Green Device is on line but has no connections in the established state.
Green Device is on line and has connections in the established state.
Flashing Red One or more I/O connections in timed-out state.
Red Critical link failure - failed communication device. Device
detected error that prevents it from communicating on the
network.
Flashing Red/Green Communication faulted device - the device has detected a
network access error and is in communication faulted state.
Device has received and accepted an Identity Communication
Faulted Request - long protocol message.
Indication Probable Cause
I/O Status
Run Status
Off Module is commanded to stop retrieving SSI data.
Green Module is commanded to retrieve SSI data.
Up Status
Off SSI data not increasing or no SSI data is being received.
Green SSI data is increasing.
Down Status
Off SSI data not decreasing or no SSI data is being received.
Green SSI data is decreasing.
Comp Status
Off Comparator function not in use or comparator value not attained.
Green Comparator value is attained.
I1 Status
Off Latching input I1 is OFF.
Green Latching input I1 is ON.