82 Rockwell Automation Publication 1734-UM017B-EN-P - October 2013
Appendix A Specifications
General Specifications
Attributes 1734-AENTR 1738-AENTR
Status indicators 3 red/green status indicators on CPU:
Module Status
Network Status (Ports 1 and 2
combined)
POINTBus Status
1 green/yellow status indicator on
CPU:
Network Activity (Ports 1 and 2)
2 green/yellow status indicators on
base:
Link 1 Activity/Status
Link 2 Activity/Status
2 green power supply status
indicators on DC-DC Converter:
System Power (5V DC to
POINTBus Out)
Field Power (24V DC from Field In)
3 red/green status indicators on CPU:
Module Status
Network Status (Ports 1 and 2
combined)
POINTBus Status
1 green/yellow status indicator on
CPU:
Network Activity (Ports 1 and 2)
2 green/yellow status indicators on
base:
Link 1 Activity/Status
Link 2 Activity/Status
2 green power supply status indicators
on DC-DC Converter:
System Power (5V DC to POINTBus
Out)
Adapter Power (24V DC from Field
In)
Wire Size Power connections: 0.34... 2.1 mm
2
(22...14 AWG) solid or stranded copper
wire rated @ 75 °C (167 °F ) or greater, 1.2 mm (3/64 in.) insulation max or
90 °C (194 °F ) for ControlLogix.
Ethernet wiring: RJ45 connector according to IEC 60603-7, 2 or 4 pair Category
5e min cable according to TIA 568-B.1 or Category 5 cable according to ISO/IEC
24702.
Power
consumption, max
10.4 W @ 28.8V DC
Wiring category
(1)
1 – on communications ports
1 – on power ports
Power dissipation,
max
6.3 W @ 28.8V DC
Input overvoltage
protection
Reverse polarity protected
Thermal
dissipation, max
21.5 BTU/hr @ 28.8V DC
Isolation voltage 50V (continuous), Reinforced
Insulation Type, between all circuits.
Type tested @ 500V AC for 60 s
50V (continuous), Basic Insulation
Type. Type Tested @ 500V AC for 60 s:
Comm to system
Comm to user power
User power to system
User power to ground
System to ground
Field power supply 10...28.8V DC @ 10A 10...28.8V DC @ 10A
Field power output 10...28.8V DC @ 9A 10...28.8V DC @ 9A
Module input 10...28V DC @ 1000 mA 10...28V DC @ 1000 mA
Dimensions
(HxWxD), approx.
76.2 x 73.0 x 133.4 mm
(3.0 x 2.87 x 5.25 in.)
112 x 123 x 67 mm
(4.41 x 4.84 x 2.64 in.)
Mounting type - Metal panel
Enclosure type
rating
None (open-style) Meets IP65/66/67/69K (when marked)
Terminal base
screw torque
0.8 Nm (7 lb-in) 0.8 Nm (7 lb-in)
Weight, approx. 0.28 Kg (0.62 lb) 0.33 Kg (0.72 lb)
(1) Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring
and Grounding Guidelines, publication 1770-IN041
and to the appropriate System Level Installation Manual.