1738 ArmorPOINT I/O EtherNet/IP Adapter 15
Publication 1738-IN031A-EN-P - July 2013
Thermal dissipation, max 9.5 BTU/hr @ 28.8V DC
Isolation voltage Type Tested @ 500V AC for 60 s:
•Comm to system
•Comm to user power
•User power to system
•User power to ground
•System to ground
Field power supply 10...28.8V DC @ 10A
Field power output 10...28.8V DC @ 9A
Module input 10...28V DC @ 1000 mA
POINTBus output, max 5V DC @ 1.0A
Dimensions (HxWxD), approx. 112.0 x 72.0 x 65.0 mm (4.41 x 2.83 x 2.56 in.)
Mounting type Metal panel
Enclosure type rating Meets IP65/66/67/69K (when marked)
Terminating base screw torque 0.8 Nm (7 lb-in)
Wiring category
(1)
1 – on power ports
1 – on communications ports
Weight, approx. 0.36 Kg (0.8 lb)
(1)
Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and
Grounding Guidelines, publication 1770-IN041.
Environmental Specifications
Attribute Value
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20...60 °C (-4...140 °F)
Temperature, ambient air, max 60 °C (140 °F)
Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal
Shock):
-40...85 °C (-40...185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5...95% noncondensing
General Specifications
Attribute Value