12 1738 ArmorPOINT I/O EtherNet/IP Adapter
Publication 1738-IN031A-EN-P - July 2013
Network
Activity
Off No link established.
Flashing
green/Off
Transmit or receive activity present.
Solid green Link established.
Network
Status
Off Device not initialized. The module does not have an IP address.
Flashing
green
No CIP connections present. Device has an IP address, but no CIP
connections are established.
Solid green CIP connections present. Device online and has an IP address, and CIP
connections are established.
Flashing red One or more CIP connections in timed-out state. Check for I/O module failure
and controller operation.
Solid red Duplicate IP address detected.
Verify IP address setting and correct, as needed.
Flashing
red/green
The module is performing a self-test (only occurs during cycle
power test).
POINTBus
Status
Off Device not powered – check module status indicator.
Flashing
red/green
LED cycle power test present.
Flashing red Recoverable fault occurred:
•At cycle power, the number of expected modules does not equal the
number of modules present.
•A module is missing.
•Node fault (I/O connection timeout) occurred.
Solid red Unrecoverable fault occurred – the adapter is bus off.
Flashing
green
Firmware (NVS) update in progress.
Solid green Adapter online with connections established (normal operation,
Run mode).
System
power
Off Not active; field power is off or DC-DC converter problem present.
Solid green System power is on; DC-DC converter is active (5V).
Adapter
power
Off Not active; field power is off.
Solid green Power is on; 24V is present.
Indicator Status for Modules
Indicator State Description