1 Publication 1734-UM007D-EN-P - December 2005
Chapter
5
Diagnose Problems
About This Chapter
Read this chapter for information about how to troubleshoot using the
module indicators.
Use the Indicators for
Troubleshooting
Use these indicators to help you troubleshoot problems with your
1734-SSI module.
Module
Status
Network
Status
1734
SSI
NODE:
RUN
UP
I1
DOWN
COMP
Module Status
Network Status
Run
Up
Comp
Down
43125
I1
Indication Probable Cause Recommended Action
Module Status
Off No power applied to device. Apply power to the device.
Solid Green Device is operating normally. None - device is operating normally.
Flashing Green Device needs commissioning due to configuration
missing, incomplete, or incorrect.
Configure device properly.
Flashing Red Recoverable fault is present. Cycle power to device. If condition persists, replace
device.
Solid Red Unrecoverable fault may require device replacement. Unrecoverable fault may require device replacement.
Flashing Red/Green Device is in self-test. None - device is in self-test.