Publication 1734-UM004F-EN-E - December 2012
Calibrate Your Module 51
10. From the General Parameters dialog, click Accept Low Calibration.
11. From the General Parameters dialog, click the Download to Device
button.
The status indicator(s) for the channel(s) being calibrated blinks.
12. Set the resistance box to 500 Ω. .
For the 1734-IR2E, set the resistance box to 200 Ω .
13. From the General Parameters dialog, click Accept High Calibration.