POINT I/O Thermocouple and RTD ModulesCatalog Numbers 1734-IR2, 1734-IR2E and 1734-IT2IUser Manual
Publication 1734-UM004F-EN-E - December 2012x Common Techniques Used in this ManualThe following conventions are used throughout this manual:•
1 Publication 1734-UM004F-EN-E - December 2012Chapter 1About POINT I/O ModulesOverviewRead this chapter to familiarize yourself with configurable feat
Publication 1734-UM004F-EN-E - December 20122 About POINT I/O ModulesSelecting a Module Input TypeThe 1734-IT2I module consists of two isolated
Publication 1734-UM004F-EN-E - December 2012About POINT I/O Modules 3Default Data Map for the Thermocouple Input Module(catalog number 1734-IT2
Publication 1734-UM004F-EN-E - December 20124 About POINT I/O ModulesData Format (1734-IT2I, 1734-IR2, and 1734-IR2E modules)You must choose a
Publication 1734-UM004F-EN-E - December 2012About POINT I/O Modules 5Use Module AlarmsPOINT I/O modules are capable of generating the following
Publication 1734-UM004F-EN-E - December 20126 About POINT I/O Modules• Low-Low•High•High-HighWhen the channel input goes below a low alarm or a
7 Publication 1734-UM004F-EN-E - December 2012Chapter 2Install the ModuleOverviewRead this chapter for information about how to install and wire RTD a
Publication 1734-UM004F-EN-E - December 20128 Install the ModuleEnvironment and EnclosureInstall the Mounting BaseThe wiring base assembly (173
Publication 1734-UM004F-EN-E - December 2012Install the Module 9You can install the assembly, or just the mounting base. Follow this procedure
Publication 1734-UM004F-EN-E - December 20122 Important User InformationSolid state equipment has operational characteristics differing from th
Publication 1734-UM004F-EN-E - December 201210 Install the Module3. Press firmly to seat the mounting base on the DIN rail.The mounting base sn
Publication 1734-UM004F-EN-E - December 2012Install the Module 111734-RTD - Position 61734-IT2I - Position 62. Make certain the DIN rail lockin
Publication 1734-UM004F-EN-E - December 201212 Install the Module3. Insert the module straight down into the mounting base and press to secure,
Publication 1734-UM004F-EN-E - December 2012Install the Module 131. Insert the RTB end opposite the handle into the base unit, which has a curv
Publication 1734-UM004F-EN-E - December 201214 Install the Module4. Remove the module to the right of the base you are removing, noting that th
Publication 1734-UM004F-EN-E - December 2012Install the Module 15Wiring Diagram Input Channel Power LimitsTo wire RTD modules, refer to the fig
Publication 1734-UM004F-EN-E - December 201216 Install the ModuleWiring DiagramChapter SummaryThis chapter explained how to install and wire th
17 Publication 1734-UM004F-EN-E - December 2012Chapter 3Configure Your ModuleOverviewThis chapter describes how to configure your thermocouple input m
Publication 1734-UM004F-EN-E - December 201218 Configure Your ModuleUsing the RSNetWorx Commissioning ToolUse the RSNetWorx commissioning tool
Publication 1734-UM004F-EN-E - December 2012Configure Your Module 19Use Sequential Auto AddressingSequential Auto Addressing (SAA) reassigns th
iii Publication 1734-UM004F-EN-E - December 2012Table of ContentsImportant User Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Publication 1734-UM004F-EN-E - December 201220 Configure Your ModuleThis chapter shows configuration in the online mode. Configuration dialogs
Publication 1734-UM004F-EN-E - December 2012Configure Your Module 21The out-of-the-box node setting for 1734 modules is 63. You can change the
Publication 1734-UM004F-EN-E - December 201222 Configure Your ModuleSet the Thermocouple Input Module Parameters Using RSNetWorxAfter adding th
Publication 1734-UM004F-EN-E - December 2012Configure Your Module 23Setting ParametersThe module name appears here.Type a description here.The
Publication 1734-UM004F-EN-E - December 201224 Configure Your ModuleConfigure Your Thermocouple Input ModuleConfiguration can be divided into t
Publication 1734-UM004F-EN-E - December 2012Configure Your Module 25Advanced Setup ParametersAdvanced parameters you can set for the thermocoup
Publication 1734-UM004F-EN-E - December 201226 Configure Your Module• Level alarms - low-low, low, high, and high-high - any value from -32,768
Publication 1734-UM004F-EN-E - December 2012Configure Your Module 27Basic Setup 1. Select the temperature scale.2. Then select the type of ther
Publication 1734-UM004F-EN-E - December 201228 Configure Your ModuleAdvanced Setup6. Select the notch filter desired (60 Hz to 480 Hz).7. Selec
Publication 1734-UM004F-EN-E - December 2012Configure Your Module 29Set the RTD Input Module Parameters Using RSNetWorx After adding the module
Publication 1734-UM004F-EN-E - December 2012iv Table of ContentsUsing the RSNetWorx Commissioning Tool. . . . . . . . . . . . . . . . . 26Use S
Publication 1734-UM004F-EN-E - December 201230 Configure Your ModuleSetting ParametersThe module name appears here.Type a description here.The
Publication 1734-UM004F-EN-E - December 2012Configure Your Module 31Configure Your RTD Input ModuleConfiguration is divided into basic and adva
Publication 1734-UM004F-EN-E - December 201232 Configure Your ModuleAdvanced Setup ParametersAdvanced parameters you can set for the RTD module
Publication 1734-UM004F-EN-E - December 2012Configure Your Module 33• Scaling – Values returned when input is at low scale value or high scale
Publication 1734-UM004F-EN-E - December 201234 Configure Your ModuleBasic Setup1. Select the type of RTD you are using for channel 0. Repeat fo
Publication 1734-UM004F-EN-E - December 2012Configure Your Module 35Advanced Setup3. Select the digital filter desired. (Range is 0...10.000 ms
Publication 1734-UM004F-EN-E - December 201236 Configure Your ModuleCheck I/O Status and View the EDS FileView the I/O defaults setup and the E
Publication 1734-UM004F-EN-E - December 2012Configure Your Module 371734-IR2 and 1734-IR2E modulesChapter SummaryThis chapter explained how to
Publication 1734-UM004F-EN-E - December 201238 Configure Your Module
39 Publication 1734-UM004F-EN-E - December 2012Chapter 4Calibrate Your ModuleOverviewUse this chapter to calibrate the thermocouple/mV module or the R
Publication 1734-UM004F-EN-E - December 2012Table of Contents vUnderstanding Data, Connection, and Communication Formats. . . . . . . . . . . .
Publication 1734-UM004F-EN-E - December 201240 Calibrate Your ModuleCalibrate the Thermocouple Input ModuleTo calibrate your thermocouple input
Publication 1734-UM004F-EN-E - December 2012Calibrate Your Module 41Access Calibration Parameters in RSNetWorx1. Double-click the icon of the m
Publication 1734-UM004F-EN-E - December 201242 Calibrate Your Module4. From the Device Parameters dialog, select Calibration at the Groups pull
Publication 1734-UM004F-EN-E - December 2012Calibrate Your Module 431. From the Configuration tab, set the Thermocouple Type to mV (no lineariz
Publication 1734-UM004F-EN-E - December 201244 Calibrate Your Module5. Click Calibration Command, and select Begin Calibration.6. Click the Dow
Publication 1734-UM004F-EN-E - December 2012Calibrate Your Module 4510. Set the source to 70 mV.Module terminal voltage must be exact.11. Click
Publication 1734-UM004F-EN-E - December 201246 Calibrate Your Module2. Click Calibration Command and select Begin CJC Calibration.3. Click the
Publication 1734-UM004F-EN-E - December 2012Calibrate Your Module 477. Select Accept High CJC and download to the device.8. If RSNetWorx report
Publication 1734-UM004F-EN-E - December 201248 Calibrate Your ModuleTools and Equipment Required to CalibrateYour RTD ModuleTo calibrate your R
Publication 1734-UM004F-EN-E - December 2012Calibrate Your Module 492. Click Device Parameters to view the parameters.The EDS editor may ask yo
Publication 1734-UM004F-EN-E - December 2012vi Table of ContentsNotes:
Publication 1734-UM004F-EN-E - December 201250 Calibrate Your Module5. From the Device Parameters dialog, select Calibration at the Groups pull
Publication 1734-UM004F-EN-E - December 2012Calibrate Your Module 5110. From the General Parameters dialog, click Accept Low Calibration. 11. F
Publication 1734-UM004F-EN-E - December 201252 Calibrate Your Module14. From the General Parameters dialog, click the Download to Device button
53 Publication 1734-UM004F-EN-E - December 2012Chapter 5Troubleshoot the ModuleOverviewRead this chapter to interpret your I/O module status indicator
Publication 1734-UM004F-EN-E - December 201254 Troubleshoot the ModuleChapter SummaryThis chapter helped you to interpret the status indicators
55 Publication 1734-UM004F-EN-E - December 2012Appendix AConfigure Modules in RSLogix 5000 SoftwareOverviewRead this appendix for information about ho
Publication 1734-UM004F-EN-E - December 201256 Configure Modules in RSLogix 5000 SoftwareOptimized Connections. They only support direct Data (
Publication 1734-UM004F-EN-E - December 2012Configure Modules in RSLogix 5000 Software 57Use the Help ButtonFrom the Configuration, Alarm Confi
Publication 1734-UM004F-EN-E - December 201258 Configure Modules in RSLogix 5000 Software2. Make entries on the dialog, referring to the table
Publication 1734-UM004F-EN-E - December 2012Configure Modules in RSLogix 5000 Software 59Alarm Configuration DialogThis dialog does not appear
vii Publication 1734-UM004F-EN-E - December 2012Summary of ChangesThis publication contains new and revised information not in the last release.New an
Publication 1734-UM004F-EN-E - December 201260 Configure Modules in RSLogix 5000 SoftwareCalibration DialogTo complete entries on this dialog,
Publication 1734-UM004F-EN-E - December 2012Configure Modules in RSLogix 5000 Software 611. Click Calibration to display the dialog.2. Check th
Publication 1734-UM004F-EN-E - December 201262 Configure Modules in RSLogix 5000 Software6. From the Low Value dialog, click Next to start cali
Publication 1734-UM004F-EN-E - December 2012Configure Modules in RSLogix 5000 Software 631. Click Configuration to display the dialog.2. Comple
Publication 1734-UM004F-EN-E - December 201264 Configure Modules in RSLogix 5000 Software Alarm Configuration DialogThis dialog does not appear
Publication 1734-UM004F-EN-E - December 2012Configure Modules in RSLogix 5000 Software 652. From the top of the dialog, at Channel click on a p
Publication 1734-UM004F-EN-E - December 201266 Configure Modules in RSLogix 5000 SoftwareCalibration DialogTo complete the entries on the Calib
Publication 1734-UM004F-EN-E - December 2012Configure Modules in RSLogix 5000 Software 674. For Calibrate Channels, select One At a Time or In
Publication 1734-UM004F-EN-E - December 201268 Configure Modules in RSLogix 5000 Software8. From the High Value dialog, click Next to start cal
69 Publication 1734-UM004F-EN-E - December 2012Appendix BCalculate Absolute Accuracy and Accuracy DriftOverviewThe Absolute Accuracy and Accuracy Drif
Publication 1734-UM004F-EN-E - December 2012viii Summary of ChangesNotes:
Publication 1734-UM004F-EN-E - December 201270 Calculate Absolute Accuracy and Accuracy DriftFull Scale ValuesUse the following full scale valu
Publication 1734-UM004F-EN-E - December 2012IndexNumerics1734 POINT I/Ooverview 1AAbsolute Accuracy 69calculate 69formula 69Accuracy Drift 69calculate
Publication 1734-UM004F-EN-E - December 201272 IndexModulesconfigure in RSLogix 5000 55modulesoverview 1mountingbase assembly 8mounting baserem
Publication 1734-UM004F-EN-E - December 2012 73
Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400Publication 1734-UM004F-EN-E - Dec
ix Publication 1734-UM004F-EN-E - December 2012PrefaceRead this preface to familiarize yourself with the rest of the manual. It provides information c