20 POINT I/O 2 Port Ethernet Adapter
Publication
1734-IN040B-EN-P - December 2009
Specifications
POINT I/O Ethernet Adapter - 1734-AENTR
Attribute Value
Expansion I/O capacity 63 modules max
5 rack optimized connections (for digital modules only)
max
20 direct connections max
1734-AENTR backplane current output = 0.8 A.
Actual number of modules can vary.
Add up current requirements of modules you want to
use to make sure they do not exceed the amperage
limit of 0.8 A for the 1734-AENTR adapter.
Backplane current can be extended beyond 0.8 A by
using 1734-EP24DC backplane extension power
supplies.
Add multiple 1734-EP24DC modules to reach the 63
module max.
POINTBus current
requirements
75 mA (Catalog numbers 1734-IB2, 1734-IB4,
1734-IB8, 1734-IV2, 1734-OB2, 1734-OB4, 1734-OB8,
1734-OB2E, 1734-OB2EP, 1734-OB4E, 1734-OB8E,
1734-OV2E, 1734-OV4E, 1734-IE2C, 1734-OE2C,
1734-IE2V, 1734-OE2V, 1734-IA2, 1734-IM2,
1734-OA2, 1734-232ASC, 1734-485ASC)
80 mA (Catalog number 1734-OW2)
100 mA (Catalog number 1734-OX2)
110 mA (Catalog number 1734-SSI)
160 mA (Catalog number 1734-IJ2)
175 mA (Catalog number 1734-IT2I)
180 mA (Catalog number 1734-VHSC5, 1734-VHSC24)
220 mA (Catalog number 1734-IR2)
Module location Starter module - left side of the 1734 system