Chapter 2 Ethernet Mode Setup
Explicit Message Example:
Follow these steps to configure an explicit message in order to retrieve the UPS output rating information.
1. Create a new "User-Defined Data Type" called "Output Rating".
2. Go to the "Controller Tags" and create a new tag called "UPS" with an "Output Rating" data type.
3. Add a new message instruction in your routine with the following parameters. Select OK once you enter all the
required parameters.
Field Value Description
Message Typ eCIP CIP Generic CIP Message
Service Type Get Get Attribute Single CIP Service
Class 377 UPS Object
Instance 1 Instance 1
Attribute 1 Attribute id 1 = 1 (hex) (Appendix B)
Destination UPS Name given to destination tag
Path ENET_Card Name given to Device