Scope These installation instructions pertain to the interlock engagement between the
isolating switch interlock lever and operating lever to determine if replacement of
a modied lever is required.
Before beginning the following procedures, refer to Publication 1500-UM055_-EN-P
for safety precautions and general information regarding Bulletin 1500/1900 controllers.
If you need a copy of the above mentioned publication, it can be found at
www.rockwellautomation.com under Resources – Literature.
Only personnel who have been trained and understand the
Bulletin 1500 product line are to work on this equipment.
Suitable safety equipment and procedures are to be used at all
times.
This procedure requires contact with medium voltage components.
To avoid shock hazards, lock out incoming power before work
-
ing on equipment. Verify with a hot stick or appropriate voltage
measuring device that all circuits are voltage free. Failure to
do so may result in severe burns, injury or death.
Always perform the power lockout procedure before servicing
the equipment. Failure to do so may result in severe burns,
injury or death.
The following procedure requires moving the isolation switch
handle to the ON position. To avoid shock hazards, disconnect
and lock out incoming power before proceeding with servicing
the equipment. Failure to lock out incoming power will result
in a live power cell once the isolation switch handle is in the
ON position and may cause severe burns, injury or death.
Rockwell Automation does not assume any responsibility for
injuries to personnel who have not completed the following
safety procedure prior to servicing the equipment.
BULLETIN 1500/1900
Isolation Switch Handle
Interlock Mechanism Replacement
INSTALLATION INSTRUCTIONS
Power Lock-out
Procedure
A T T E N T I O NA T T E N T I O N
A T T E N T I O NA T T E N T I O N
A T T E N T I O NA T T E N T I O N
A T T E N T I O NA T T E N T I O N
Zobrazit stránku 0
1 2 3 4 5 6 ... 19 20

Shrnutí obsahu

Strany 1 - BULLETIN 1500/1900

Scope These installation instructions pertain to the interlock engagement between the isolating switch interlock lever and operating lever t

Strany 2 - Procedure (cont.)

10 Bulletin 1500/1900 Isolation Switch Handle – Interlock Mechanism Replacement1500-IN052C-EN-P – January 2007Procedure for Operating Lever Replaceme

Strany 3

Bulletin 1500/1900 Isolation Switch Handle – Interlock Mechanism Replacement 111500-IN052C-EN-P – January 2007Procedure for Operating Lever Replace

Strany 4 - Incoming Line Stabs

12 Bulletin 1500/1900 Isolation Switch Handle – Interlock Mechanism Replacement1500-IN052C-EN-P – January 2007Procedure for Operating Lever Replaceme

Strany 5

Bulletin 1500/1900 Isolation Switch Handle – Interlock Mechanism Replacement 131500-IN052C-EN-P – January 2007Procedure for Operating Lever Replace

Strany 6 - − remove both Washers

14 Bulletin 1500/1900 Isolation Switch Handle – Interlock Mechanism Replacement1500-IN052C-EN-P – January 2007Replaced Retrot Operating Lever Conn

Strany 7 - 2) Remove the Flat Washer

Bulletin 1500/1900 Isolation Switch Handle – Interlock Mechanism Replacement 151500-IN052C-EN-P – January 2007 To avoid shock hazards, lock out i

Strany 8

16 Bulletin 1500/1900 Isolation Switch Handle – Interlock Mechanism Replacement1500-IN052C-EN-P – January 2007 To Reduce the Gap Distance 5) Loos

Strany 9 - Operating Lever

Appendix A1500-IN052C-EN-P – January 2007Door Interlock Circumvention The door interlock mechanism is designed to prevent access to the medium volt

Strany 10 - Retrofit Operating Lever

A-2 Door Interlock Circumvention1500-IN052C-EN-P – January 2007This page is intentionally left blank.

Strany 12

2 Bulletin 1500/1900 Isolation Switch Handle – Interlock Mechanism Replacement1500-IN052C-EN-P – January 2007 1) Disconnect and lock out all feeder

Strany 13

Medium Voltage Products, 135 Dundas Street, Cambridge, ON, N1R 5X1 Canada, Tel: (1) 519.740.4100, Fa

Strany 14

Bulletin 1500/1900 Isolation Switch Handle – Interlock Mechanism Replacement 31500-IN052C-EN-P – January 2007 Grounding BarIsolation Switch Bladesm

Strany 15 - Adjustment

4 Bulletin 1500/1900 Isolation Switch Handle – Interlock Mechanism Replacement1500-IN052C-EN-P – January 2007Isolation Switch Bladesmust fully engage

Strany 16 - Adjustment (cont.)

Bulletin 1500/1900 Isolation Switch Handle – Interlock Mechanism Replacement 51500-IN052C-EN-P – January 2007Procedure for Operating Lever Replacem

Strany 17 - Appendix A

6 Bulletin 1500/1900 Isolation Switch Handle – Interlock Mechanism Replacement1500-IN052C-EN-P – January 2007Procedure for Operating Lever Replacemen

Strany 18

Bulletin 1500/1900 Isolation Switch Handle – Interlock Mechanism Replacement 71500-IN052C-EN-P – January 2007Procedure for Operating Lever Replacem

Strany 19

8 Bulletin 1500/1900 Isolation Switch Handle – Interlock Mechanism Replacement1500-IN052C-EN-P – January 2007Procedure for Operating Lever Replacemen

Strany 20 - P/N 80050-167 (1)

Bulletin 1500/1900 Isolation Switch Handle – Interlock Mechanism Replacement 91500-IN052C-EN-P – January 2007Procedure for Operating Lever Replacem

Komentáře k této Příručce

Žádné komentáře