8 XM-947 Dynamic Vibration Terminal Base
Publication GMSI10-IN027A-EN-P - May 2010
14 to 22 AWG copper conductors without pretreatment; 8 AWG
required for grounding the DIN rail for electromagnetic interference
(emi) purposes
Recommended strip length 8 millimeters (0.31 inches)
Minimum insulation rating of 300V
Soldering the conductor is forbidden
Wire ferrules can be used with stranded conductors; copper ferrules
recommended
Grounding Requirements
Use these grounding requirements to ensure safe electrical operating
circumstances, and to help avoid potential emi and ground noise that can
cause unfavorable operating conditions for your XM system.
DIN Rail Grounding
The XM modules make a chassis ground connection through the DIN rail.
The DIN rail must be connected to a ground bus or grounding electrode
conductor using 8 AWG or 1 inch copper braid. See illustration on the
following page.
Use zinc-plated, yellow-chromated steel DIN rail (Allen-Bradley part no.
199-DR1 or 199-DR4) or equivalent to assure proper grounding. Using other
DIN rail materials (e.g. aluminum, plastic, etc.), which can corrode, oxidize, or
are poor conductors can result in improper or intermittent platform
grounding.
ATTENTION
See the XM Documentation and Configuration Utility CD for Hazardous
Locations installation drawings. The XM Documentation and Configuration
Utility CD is packaged with the XM modules.