Trusted
TM
Module T8472
Issue 13 Sep 11 PD-T8472 12
2.2. Field Power Connection
May be connected at the T8871 Field Termination Adapter. However Field Power may be connected
any where along the cable by pulling the Field Power Cables (Grey & White) out of the outer sheath
a
nd connecting onto suitable junction boxes.
2.2.1. Cable Impedance
Custom length multi-core FTA cables are 0.5mm
2
with a resistance of 40M/km. eg a 50m cable will
have 4M loop impedance at 0.5A, this equates to a 2Vdc volt drop.
2.3. Termination
Unused channels should be commanded OFF and may be fitted with a 33k 2W resistor to prevent no-
load detection.
2.4. Module Pinout Connections
Field Connections are made to the Modules DIN41612 type D Field Connector:
Table 2 Field Connector Pin-Out
Pin No. Row a Row c
2 (SMART_SLOT_A) (SMART_SLOT_B)
4 (SMART_SLOT_C) spare
6 V_RET_CH9_16 V_RET_CH1_8
8 V_FIELD_CH9_16 V_FIELD_CH1_8
10 V_FIELD_CH9_16 V_FIELD_CH1_8
12 V_FIELD_CH9_16 V_FIELD_CH1_8
14 V_FIELD_CH9_16 V_FIELD_CH1_8
16 V_FIELD_CH9_16 V_FIELD_CH1_8
18 LOAD_CH9 LOAD_CH1
20 LOAD_CH10 LOAD_CH2
22 LOAD_CH11 LOAD_CH3
24 LOAD_CH12 LOAD_CH4
26 LOAD_CH13 LOAD_CH5
28 LOAD_CH14 LOAD_CH6
30 LOAD_CH15 LOAD_CH7
32 LOAD_CH16 LOAD_CH8