Analog Output Modules
(T7470A)
PD
-
7025
Mar
-
06
13
precision load resistors to the analog outputs. Figure
9
shows
the jumper posts to which you should connect the precision
resistors for each analog output channel.
Figure
9
. I/O Extender Connections for Analog Output Calibration.
Within each pair of jumper posts, make sure that you connect
the resistors to the jumper posts nearest the front of the I/O
extender. Do not make any connections to the jumper posts
nearest the I/O chassis backplane
these connect to the
actual field wiring attached to the I/O slot terminals on the I/O
chassis.
Calibration Steps
1.
Remove the module to be calibrated from the I/O chassis.
Important!
Zobrazit stránku 12