Rockwell-automation T7411 ICS Regent+Plus Monitored Digital Input Modu Uživatelský manuál Strana 12

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 23
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 11
Monitored Digital Input Modules
(T741
1)
12
Industrial Control Services
Figure
7
. Line Monitoring, Single Switch Connected to
Redundant Modules.
With the line monitor device installed, the input voltage, V
in
,
has four possible states as represented in Table
1
. When the
input module reads the input, the reference voltage, V
ref
, is
set to the values shown in Table
1
to detect the state of the
field input and wiring.
Table
1
. Input States and Reference Voltage Thresholds.
V
ref
Threshold
Voltage
V
in
with Line
Monitor
V
in
without
Line Monitor
Stuck
-
on Test
32 Vdc
24 Vdc
Wire Open
Switch Open
Open Circuit
20 Vdc
16 Vdc
Switch Open
NA
On/Off
12 Vdc
8 Vdc
Switch Closed
NA
Short Circuit
4 Vdc
0 Vdc
Wire Short
Switch Closed
Stuck
-
Off Test
-
5 Vdc
Zobrazit stránku 11
1 2 ... 7 8 9 10 11 12 13 14 15 16 17 ... 22 23

Komentáře k této Příručce

Žádné komentáře