(T3461A, 62A, 68A) DC Guarded Digital Output Modules
PD
-
6019
Mar
-
06
7
Blown Fuse Indicators
The red BLOWN FUSE indicators switch on when the
adjacent front panel fuse opens. If all four fuses in a group
have opened, all of the BLOWN FUSE indicators will switch
off and the condition will be annunciated by the module’s
FAULT indicator, which will be on.
Applicatio
n
Guarded digital output modules provide a suitable interface to
safety
-
critical output devices. These safety
-
critical devices
typically include solenoids, actuators, or other process
interlock outputs. Guarded output modules can be used for
fail
-
safe or fault tolerant operation.
Fail
-
Safe Configuration
As shown in Figure
3
, fail
-
safe configuration uses a single
Guarded module. In this configuration, the worst case failure
will cause the output to fail to the off state.
In a fail
-
s
afe configuration, removing the module disables all
outputs.
Figure
3
. Fail
-
Safe Configuration.
Fault Tolerant Configuration
For fault tolerant operation, two Guarded modules are
connected in parallel as shown in Figure
4
. In this
configuration, operation continues even if one module fails.