Monitored Digital Input Modules
, T
ype F (T3411F, T3418F)
14
Industrial Control Services
Line Monit
oring
For DC powered inputs, the monitored digital input module
can perform line monitoring of the field wiring when a
suitable line monitor device is installed across the field input
switch. A variety of line monitor devices are available to
match the voltage and input redundancy used in the
application.
Figure
8
shows a single switch connected to a single monitored
input module. This type of configuration uses a line monitor
device which contains two resistors, one in series
with the field
switch and one in parallel with the field switch. Figure
8
also
applies to fault tolerant input configurations that include
redundant sensors connected to redundant input modules.
Figure
8
. Line Monitoring, Single Switch Connected to
Single Module.