Publication RA-UM002B-EN-P - November 2010
Using the E3 Module 35
E3 Operational Parameters
The following is a list of all parameters that must be set correctly in the E3. All
others that are not in this list should be left at their default value or do not take
effect with the E3p_AOI.
General Parameters
Parameter Description Required Setting
24 Trip enable See graphic on page 36
25 Warning enable See graphic on page 36
27 Single/three phase Three phases
28 FLA setting Full load amps from the motor nameplate
30 OL/PTC reset mode Manual
E3 will not reset automatically
31 OL reset level 75% (default)
User will not be able to reset E3 until therm util. is
below this value.
32 OL warning level 85% (default)
E3 will show an overload warning when therm util.
is equal or above this value.
59 Output assembly 105
60 Input assembly 100
61 Assy word 0 21 (device status)
62 Assy word 1 14 (trip status)
63 Assy word 2 4 (Therm. Util.)
64 Assy word 3 9 (Average current)