MBB
October
200
5
Issue 4
T
riguard
SC300E
EXTENSION CHASSIS ADDRESSING
The
chassis
address
is
set
up
on
links
on
the
chassis
backplane.
The
physical
locations
of
the
links
are
indicated
by
small
triangles
in
columns
‘b’
and
‘c’
of
areas
‘d’
in
Figure
2
-
3.
On
the
chassis
backplane
the
links
are
identified
as
UNIT
ID0
to
UNIT
ID3.
The
presence
of
a link
sets
the
corresponding
address
bit
to
‘0’.
If
a link
is
absent
the
corresponding
address
bit
is
a ‘1’.
The
full
range
of
chassis
address
link
settings
is
given
in
Figure
2
-
5.
POWER SUPPLIES
A pair
of
auctioneering
diodes
combines
the
two
5.4Vdc
power
supplies
from
the
chassis
-
mounted
PSUs
into
a single
5Vdc
(nominal)
supply
for
the
whole
module.
The
12V
outputs
from
the
chassi
s
-
mounted
PSUs
are
not
used
by
the
MBB.
A ‘power
on
clear’
pulse
resets
the
control
logic
when
the
power
supply
first
comes
on
line.