37Operation
Before applying power (all models)
ATTENTION: If the motor or drive does not perform
as described, disconnect the AC line voltage
immediately. Refer to the Troubleshooting section,
page 67, for further assistance.
Set LINE VOLTAGE SELECT switches SW501 and
SW502 to either 115V or 230V to match the AC line
voltage.
Set ARMATURE VOLTAGE SELECT switch SW503 to
either 90V or 180V to match the maximum armature
voltage.
Set SIGNAL SELECT switch SW504 to CURR if using
a 4-20 mADC current signal; set it to VOLT if using a
0-10 VDC voltage signal or the speed adjust
potentiometer.
Verify that no conductive material is present on the
printed circuit board.
If using a 90 VDC or 130 VDC motor with 230 VAC
line voltage, derate the nameplate motor speed and
torque by at least 30%. The form factor will increase
beyond the typical value, causing increased motor
heating. Contact the factory for details.