Document: 553632
(ICSTT-RM448_EN_P) Issue: 08:
4-5
Step Task
Force Will remain OFF as the Module boots up (10 to 20 seconds) then stays
OFF until the module has educated.
Aux Will remain OFF as the Module boots up (10 to 20 seconds) then is
dependent upon data connection.
Serial 1 Will remain OFF as the Module boots up (10 to 20 seconds) then is
dependent upon data connection
Serial 2 Will remain OFF as the Module boots up (10 to 20 seconds) then is
dependent upon data connection
Ethernet 1 Will remain OFF as the Module boots up (10 to 20 seconds) then is
dependent upon data connection
Ethernet 2 Will remain OFF as the Module boots up (10 to 20 seconds) then is
dependent upon data connection
You have to set up the processor IP Address so that the workstation can communicate with the
processor module and download the latest firmware build and configure the processor variables.
3. Set the Controller IP Address for all the processor modules using the "AADvance Discover
Utility". (Refer to the Configuration Guide for detailed instructions on using the AADvance
Discover Utility Doc. No: 553633).
4. Install a Program Enable Key. Download a valid application and press the FAULT RESET
button. When the application is downloaded and valid the module will display the following
indications:
Valid Application Downloaded
Healthy GREEN
Ready GREEN
Run RED to GREEN (Flashes GREEN as the module educates)
System Healthy GREEN
Force GREEN
Aux Off (Application Dependent)
Serial 1 Dependent on data connection
Serial 2 Dependent on data connection
Ethernet 1 Dependent on data connection
Ethernet 2 Dependent on data connection
Zobrazit stránku 84