Each application program, or task, that wishes to reference the
symbolic names assigned to the input module may do so by
declaring those names COMMON.
The frequency with which tasks read their inputs and write their
outputs depends on the language being used. Control block tasks
read inputs once at the beginning of each scan and write outputs
once at the end of scan. BASIC tasks read an input and write an
output for each reference throughout the scan.
The following is an example of a configuration task for the input
module:
1000 !
1001 ! resolver input
1002 !
1005 IODEF RESOLVER_IN%[SLOT=4, REGISTER=0]
1006 IODEF RESOLVER_IN_EXT%[SLOT=4, REGISTER=1]
1010 !
1011 ! common clock enable
1012 !
1015 IODEF CCLK_EN@[SLOT=4, REGISTER=3, BIT=6]
1020 !
1021 ! A/D update period
1022 !
1025 IODEF UPDATE_TIME%[SLOT=4, REGISTER=4]
1050 !
1051 ! Place any additional configurationăstatements here
1052 !
2000 END
4.4.1 BASIC Task Example
This example will read the resolver input once every second and
store the value in the symbol CURRENT_VALUE". The resolver
position will be sampled every 100 milliseconds.
1000 COMMON RESOLVER_IN% \!Resolver data(periodic)
1010 COMMON CCLK_EN@ \!common clock enable
1020 COMMON UPDATE_TIME% \!Update period for resolver conversion
1400 !
1500 LOCAL CURRENT_VALUE% \!Current value of analog input
1900 !
2000 UPDATE_TIME% = 200 \!0.1 second conversion
2010 CCLK_EN@ = TRUE \!turn on the clock
4000 !
4001 ! Place any additional initialization software here
4002 !
5000 START EVERY 1 SECONDS
5010 CURRENT_VALUE% = RESOLVER_IN%
10000 END
The symbolic names defined as COMMON" reference the inputs
defined in the sample configuration task above. The symbolic name
CURRENT_VALUE% is local to the BASIC task and does not have I/O
associated with it. Refer to the DCS 5000 Enhanced BASIC
Language Instruction Manual (JĆ3600) for more information.
4.4.2 Control Block Task Example
The following example will read the resolver data every 55
milliseconds and store the inverted value in the symbol READING".
The resolver's shaft position will be sampled every 500
microseconds.
1000 COMMON RESOLVER_IN% \!Resolver data (periodic)
1010 COMMON CCLK_EN@ \!Common clock enable
1020 COMMON UPDATE_TIME% \!Update period forĂresolver conv.
1400 !
1500 LOCAL READING% \!Current negative value of input
1600 !