Page 30 AutoMax DCSNet /RE RIO Module
Publication number 56AMXN-UM002A-EN-P November 2002
Figure 9 Module Properties 1
3. Assign the module a Name and optionally a Description.
4. Set the Comm Format to Input Data – INT – With Status
5. Set the Slot to match the slot number of the 56AMXN module in
the chassis.
6. The Input Assembly Instance should be 1. The size should be
large enough to allow all the data to be passed (or larger). The
maximum size is 250 words. The minimum size is determined
by the largest offset assigned to input data.
7. The Output Assembly Instance should be 3. You cannot set the
size.
8. The Configuration Assembly Instance should be 4. The size
should be 4.
9. The Status Input Assembly Instance should be 5. The size should
be large enough to allow all the data to be passed (or larger).
The maximum size is 250 words. For Remote I/O master
operation, set the size to 1.
10. The Status Output Assembly Instance should be 6. You cannot
set the size.
11. Click Next > to display the second Module Properties – Local
dialog box.