Chapter 4 Bulletin 290E/291E/294E Programmable Parameters
Clear a Type 1 Fault and Restart the Drive
1. Set Parameter 84 (AutoRestartTries) to a value other than 0.
2. Set Parameter 85 (AutoRestartDelay) to a value other than 0.
Clear an Overvoltage, Undervoltage, or Heatsink OvrTmp Fault without Restarting the Drive
1. Set Parameter 84 (AutoRestartTries) to a value other than 0.
2. Set Parameter 85 (AutoRestartDelay) to 0.
AutoRstrtTries
Set the maximum number of times the drive
attempts to reset a fault and restart.
Parameter Number 84
Related Parameter 85
Access Rule GET/SET
Data Type UINT
Group Advanced Config.
Units —
Minimum Value 0
Maximum Value 9
Default Value 0
ATTENTION: Equipment damage and/or personal injury may result if this
parameter is used in an inappropriate application. Do not use this function
without considering applicable local, national, and international codes,
standards, regulations, or industry guidelines.