Troubleshooting 11-21
Base Module Replacement
(Bulletin 284)
Installation of Base Module
1) Mount Base Module with four mounting screws.
2) Re-install conduit fittings and wires onto terminal block.
3) Tighten terminal screws.
4) Install terminal cover plate.
5) Tighten four mounting screws on the terminal access cover plate.
6) Install Control Module.
7) Tighten four mounting screws.
8) Install all cables to Control Module, comunication cables and all
others connected to the inputs and outputs.
Figure 11.6 Bulletin 284 Base Module Installation
ATTENTION
!
To avoid shock hazard, disconnect main power
before working on the controller, motor, or control
devices
4
3
1
2
5
6
7
7
Input/
Output
Cable
Communication
Cable
Motor
Cable
Control
Module
Terminal Access
Cover Plate
Base Module
Base Module
12 lb - in./1.36 Nm