PanelView™ e Transfer Utility(Cat. No. 2711E-ND7)User Manual
1–2 Introducing the PanelView e Transfer Utility 32When the splash screen disappears, the following maindownload/upload dialog box is displayed.The Pa
6–12 Troubleshooting for the PanelView e Transfer Utility 32Messages/General Types of Messages What to doCauseCommunications hardware or driver notpre
Appendix AConstructing the Transfer PathThis appendix explains how to construct the transfer path in thePanelView e Transfer Utility 32 for network a
Constructing the Transfer PathA–2The format of the transfer path on remote DH+ networks is:Transfer Path Format Valid Entriesll.rrr.ssll local KA addr
Constructing the Transfer Path A–3The valid transfer paths for the various PanelView terminals in thefigure are:PanelView Address Valid Transfer Path2
Constructing the Transfer PathA–4The format of the transfer path on a remote DH+ network is:Transfer Path Format Valid Entriesll:rrrrr.ssll local PI a
Constructing the Transfer Path A–5Figure A.2 Multiple DH+ Networks Connected by a PI LinkKAPI Chassis10DH+23Link 4Link 23RMLink 11211BridgeAddress1EID
IndexI–1Publication 2711E-6.16Symbols*.csv file, 3-8*.pvd file, 1-3Numbers1770ĆKF2, 2-41770ĆKFC, 2-81784ĆKL, 2-41784ĆKTC, 2-81784ĆKTCX, 2-81784ĆKTK1,
IndexI–2Publication 2711E-6.16EError checking, 5-9, 5-12, 5-15Error message, 6-1ErrorĆdetection protocol, 5-9, 5-12,5-15Ethernetequipment required for
IndexI–3Publication 2711E-6.16Publications, related, P-2Pyramid Integrator, bridging DH+networks, A-4RRack assignments, 1-5Refresh List button, 5-11,
Publication 2711E-UM003B-EN-P - September 2001 PN 41061-138-01(
1–3Introducing the PanelView e Transfer Utility 32You can transfer terminal application files, whose names end in .pvd,using the PanelView e Transfer
1–4 Introducing the PanelView e Transfer Utility 32To do network downloads, you can use RSLinx drivers. RSLinx Liteis included on floppy disks with yo
1–5Introducing the PanelView e Transfer Utility 32• Do not try to download application files from two developmentcomputers to the same location at the
1–6 Introducing the PanelView e Transfer Utility 32PanelView e Transfer Utility 32 and RSLinxThe Transfer Utility supports RSLinx network drivers. RSL
1–7Introducing the PanelView e Transfer Utility 32If your version of INTERCHANGE is earlier than 6.1.0, you mustview and configure the ports outside o
Chapter 2Publication 2711E-UM003B–EN–PWorking with the PanelView eTransfer Utility 32This chapter provides instructions for setting up and using thePa
2–2 Working with the PanelView e Transfer Utility 32Publication 2711E-UM003B–EN–PPanelBuilder ApplicationsFor details about PanelBuilder applications,
2–3Working with the PanelView e Transfer Utility 32Publication 2711E-UM003B–EN–PThis section describes the equipment required to perform thefollowing
2–4 Working with the PanelView e Transfer Utility 32Publication 2711E-UM003B–EN–PDH+ Network TransfersYou need one of the following Allen-Bradley Data
Important User InformationBecause of the variety of uses for the products described in this publication, those responsible for the application and use
2–5Working with the PanelView e Transfer Utility 32Publication 2711E-UM003B–EN–PFigure 2.2 DH+ Network Download (with KF2)
2–6 Working with the PanelView e Transfer Utility 32Publication 2711E-UM003B–EN–PFigure 2.3 DH+ Network Download (with 1784-KT card)
2–7Working with the PanelView e Transfer Utility 32Publication 2711E-UM003B–EN–PFigure 2.4 DH+ Network Download (with Logix55xx)
2–8 Working with the PanelView e Transfer Utility 32Publication 2711E-UM003B–EN–PControlNet Network TransfersThe 1200e terminals are not compatible wi
2–9Working with the PanelView e Transfer Utility 32Publication 2711E-UM003B–EN–PFigure 2.5 ControlNet Network Download (with 1770-KFC)
2–10 Working with the PanelView e Transfer Utility 32Publication 2711E-UM003B–EN–PFigure 2.6 ControlNet Network Download (with 1784-KTC or KTCX card)
2–11Working with the PanelView e Transfer Utility 32Publication 2711E-UM003B–EN–PFigure 2.7 ControlNet Network Download (with Logix55xx)
2–12 Working with the PanelView e Transfer Utility 32Publication 2711E-UM003B–EN–PRemote I/O Pass-Through TransfersThe Remote I/O Pass-Through feature
2–13Working with the PanelView e Transfer Utility 32Publication 2711E-UM003B–EN–PFigure 2.8 Remote I/O Pass-Through on a DH+ Network
2–14 Working with the PanelView e Transfer Utility 32Publication 2711E-UM003B–EN–PFigure 2.9 Remote I/O Pass-Through on a ControlNet Network (with 177
Publication 2711E-6.16PrefaceBefore You Begin P–1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Purpose of This Manual P–1.
2–15Working with the PanelView e Transfer Utility 32Publication 2711E-UM003B–EN–PFigure 2.10 Ethernet Remote I/O Pass-Through
2–16 Working with the PanelView e Transfer Utility 32Publication 2711E-UM003B–EN–PYou can install the PanelView e Transfer Utility 32 software usingth
2–17Working with the PanelView e Transfer Utility 32Publication 2711E-UM003B–EN–PPanelView e Transfer Utility 32 (FTU32) Version 5 is provided onthe P
2–18 Working with the PanelView e Transfer Utility 32Publication 2711E-UM003B–EN–PThe CD-ROM includes two install versions for the TransferUtility sof
2–19Working with the PanelView e Transfer Utility 32Publication 2711E-UM003B–EN–P6. In the Choose Applications dialog box, choose to install theTransf
2–20 Working with the PanelView e Transfer Utility 32Publication 2711E-UM003B–EN–P11. Choose the program folder (program group) in which you want toin
2–21Working with the PanelView e Transfer Utility 32Publication 2711E-UM003B–EN–PPanelView 1200/1400e Transfer Utility (FTU) Version 3 is providedon t
2–22 Working with the PanelView e Transfer Utility 32Publication 2711E-UM003B–EN–P6. In the Choose Applications dialog box, choose File TransferUtilit
2–23Working with the PanelView e Transfer Utility 32Publication 2711E-UM003B–EN–P13. After all the applications have completed installing, you areprom
2–24 Working with the PanelView e Transfer Utility 32Publication 2711E-UM003B–EN–P7. Choose the program folder (program group) in which you want toins
Table of Contentstoc–iiPublication 2711E-6.16Chapter 3Uploading PanelView 1000e/1200e/1400e Application Files 3–1. . . . . . Uploading the PanelView 1
2–25Working with the PanelView e Transfer Utility 32Publication 2711E-UM003B–EN–P3. Browse the CD for file “FTU_V3”. Browse Disk 1. Run“SETUP.EXE”.If
2–26 Working with the PanelView e Transfer Utility 32Publication 2711E-UM003B–EN–PDo not cancel the installation while it is in progress. If you want
2–27Working with the PanelView e Transfer Utility 32Publication 2711E-UM003B–EN–PIf you have problems running the Transfer Utility and you havehad pre
2–28 Working with the PanelView e Transfer Utility 32Publication 2711E-UM003B–EN–PTo start the FTU32 from PanelBuilder 1400e:" In the PanelBuilde
2–29Working with the PanelView e Transfer Utility 32Publication 2711E-UM003B–EN–PThe PanelView 1200/1400e Transfer Utility Version 3 (FTU) includestwo
2–30 Working with the PanelView e Transfer Utility 32Publication 2711E-UM003B–EN–PIf you have problems running the File Transfer Utility and youhave h
2–31Working with the PanelView e Transfer Utility 32Publication 2711E-UM003B–EN–PWhen you have finished transferring applications, exit the PanelView1
Chapter 3Uploading 1000e/1200e/1400eApplication Files and AlarmHistory FilesThis chapter describes how to upload PanelView application filesand alarm
3–2 Uploading 1000e/1200e/1400e Application Files and Alarm History FilesTo prepare the PanelView terminal for a serial upload:1. Using the hardware k
3–3Uploading 1000e/1200e/1400e Application Files and Alarm History Files5. To transfer an application serially, in the Terminal Configurationscreen, c
PrefacePrefaceWelcome to the Allen-Bradley PanelView e Transfer Utility 32. Withthis software, you can transfer PanelBuilder applications to and froma
3–4 Uploading 1000e/1200e/1400e Application Files and Alarm History Files2. In the Terminal Configuration screen, choose the TerminalNetwork Setup but
3–5Uploading 1000e/1200e/1400e Application Files and Alarm History Files2For Remote I/O applications, you can change the baud rate. Thefollowing shows
3–6 Uploading 1000e/1200e/1400e Application Files and Alarm History FilesTo configure the PanelView e Transfer Utility 32 for the upload:1. In the Pan
3–7Uploading 1000e/1200e/1400e Application Files and Alarm History FilesIf you want the file to upload with the same name as the selectedupload file,
3–8 Uploading 1000e/1200e/1400e Application Files and Alarm History FilesThe PanelView e Transfer Utility 32 allows you to upload anapplication’s hist
3–9Uploading 1000e/1200e/1400e Application Files and Alarm History FilesBox DataAlarm TriggerSigned long integer valueAlarm Message The alarm message
3–10 Uploading 1000e/1200e/1400e Application Files and Alarm History FilesUploading the Alarm History FilesTo upload alarm history files, you must com
3–11Uploading 1000e/1200e/1400e Application Files and Alarm History Files4. When you have selected the required settings, choose OK to exitthis screen
3–12 Uploading 1000e/1200e/1400e Application Files and Alarm History Files2. In the Terminal Configuration screen, choose the TerminalNetwork Setup bu
3–13Uploading 1000e/1200e/1400e Application Files and Alarm History Files2For Remote I/O application files, you can change the baud rate.The following
PrefaceP–2Contents of This ManualChapter Title ContentsPreface An overview of this manual and a list of relatedpublications.1 Introducing thePanelVie
3–14 Uploading 1000e/1200e/1400e Application Files and Alarm History FilesTo configure the PanelView e Transfer Utility 32 for the upload:1. In the Pa
3–15Uploading 1000e/1200e/1400e Application Files and Alarm History FilesIf you want the file to upload with the same name as the selectedupload file,
3–16 Uploading 1000e/1200e/1400e Application Files and Alarm History Files8. To save your settings, choose System Options from the Optionsmenu, or fr
Chapter 4Downloading1000e/1200e/1400eApplication FilesThis chapter describes how to download application files using thevarious transfer methods descr
4–2 Downloading 1000e/1200e/1400e Application FilesTo prepare the PanelView terminal for a serial download:1. Using the hardware keyswitch or the Goto
4–3Downloading 1000e/1200e/1400e Application FilesTo prepare the PanelView terminal for a network download:1. To use the Current Application’s transfe
4–4 Downloading 1000e/1200e/1400e Application FilesIn the examples below, the first screen displays a ControlNettransfer setup. The second screen disp
4–5Downloading 1000e/1200e/1400e Application Files7. Switch the PanelView terminal to Run mode. The ApplicationTransfer screen is displayed. You can n
4–6 Downloading 1000e/1200e/1400e Application Files3. Choose RIO Pass-Through as the Address Source. When youchoose RIO Pass-Through, the configuratio
4–7Downloading 1000e/1200e/1400e Application FilesTo configure the PanelView e Transfer Utility 32 for the download:1. In the PanelView e Transfer Uti
Preface P–3For Publication NumberSeeA complete list of current Allen-Bradleydocumentation, including ordering instructions.Also indicates whether the
4–8 Downloading 1000e/1200e/1400e Application FilesIf you do not want to format the storage area or if you cannotformat the storage area, the followin
4–9Downloading 1000e/1200e/1400e Application Files5. Select or clear the following download options:Download Option DescriptionOverwrite Existing File
4–10 Downloading 1000e/1200e/1400e Application Files6. Click OK to save the settings and exit from the File TransferOptions dialog box.7. Configure co
Chapter 5Configuring CommunicationsSettings for 1000e/1200e/1400eApplication TransfersThis chapter provides instructions for configuring communication
5–2 Configuring Communications Settings for 1000e/1200e/1400e Application TransfersFTU32 Version 5 Table 5.A Table of PC Host Hardware and
5–3Configuring Communications Settings for 1000e/1200e/1400e Application TransfersIf you have thiscommunicationhardwareSelect the corresponding driver
5–4 Configuring Communications Settings for 1000e/1200e/1400e Application TransfersIf you have thiscommunicationhardwareSelect the corresponding drive
5–5Configuring Communications Settings for 1000e/1200e/1400e Application TransfersTo select the transfer method:" In the main download/upload dia
5–6 Configuring Communications Settings for 1000e/1200e/1400e Application TransfersTo obtain transfer parameter values using an application file:1. Ch
5–7Configuring Communications Settings for 1000e/1200e/1400e Application Transfers4. Click Apply. The transfer path, network type, and driver valuesfr
PrefaceP–4If you have questions about the PanelView e Transfer Utility 32,consult the online help and user documentation first. If you can’t findthe
5–8 Configuring Communications Settings for 1000e/1200e/1400e Application TransfersSerial Transfer Method — Driver ConfigurationWhen you select Serial
5–9Configuring Communications Settings for 1000e/1200e/1400e Application Transfers3. Select the Configure Driver button.For Serial 1 or Serial 2, the
5–10 Configuring Communications Settings for 1000e/1200e/1400e Application TransfersNetwork Transfer Method — Network and Driver ConfigurationWhen you
5–11Configuring Communications Settings for 1000e/1200e/1400e Application TransfersBefore the RSLinx driver appears on the driver list, you must first
5–12 Configuring Communications Settings for 1000e/1200e/1400e Application TransfersParitySpecify None or Even for the type of error-checking to be us
5–13Configuring Communications Settings for 1000e/1200e/1400e Application TransfersRemote I/O Pass-Through — Network, Driver, andPass-Through Setup Co
5–14 Configuring Communications Settings for 1000e/1200e/1400e Application TransfersDriver options include serial and RSLinx ports. When selecting adr
5–15Configuring Communications Settings for 1000e/1200e/1400e Application TransfersPortSpecify COM1, COM2, COM3, or COM4 as the serial port usedto con
5–16 Configuring Communications Settings for 1000e/1200e/1400e Application TransfersTo set the transfer path using Runtime PV File:" See “Obtain
Chapter 6Troubleshooting for thePanelView e Transfer Utility 32This chapter describes how to diagnose and solve problems youmight encounter while tran
Chapter 1Introducing the PanelView eTransfer Utility 32This chapter introduces you to the PanelView e Transfer Utility 32,version 5, including:• what
6–2 Troubleshooting for the PanelView e Transfer Utility 32Problem What to doCauseApplication file won’t download or upload. The computer
6–3Troubleshooting for the PanelView e Transfer Utility 32Use the following table to identify communication problems youmay encounter.Problem Cause Wh
6–4 Troubleshooting for the PanelView e Transfer Utility 32Use the following table to identify Transfer Utility problems youmay encounter due to *.pvd
6–5Troubleshooting for the PanelView e Transfer Utility 32Problem What to doCauseUnable to read application header details fromthe PVD file “%s”.This
6–6 Troubleshooting for the PanelView e Transfer Utility 32Problem What to doCauseNo ControlNet (KTCs) driver found on PanelViewterminal.The download
6–7Troubleshooting for the PanelView e Transfer Utility 32Problem What to doCauseHost PC failed to communicate with PanelViewterminal. Error code RDM
6–8 Troubleshooting for the PanelView e Transfer Utility 32Problem What to doCauseThe application %s of %s type cannot run on a%s type terminal. The a
6–9Troubleshooting for the PanelView e Transfer Utility 32Use the following table to identify Transfer Utility problems youmay encounter due to driver
6–10 Troubleshooting for the PanelView e Transfer Utility 32Message What to doCauseMight not be accessing COM port. Check other program or devices tha
6–11Troubleshooting for the PanelView e Transfer Utility 32Message What to doCauseDuring a pass-through download or upload,the DH+ cable is not connec