6-4 Using the Serial Port
Variable Data [CTRL][V]
Use the CTRL-V command to send data for display in Binary, BCD,
Numeric, Priority, and Round Robin modes. All values are decimal values.
The command has the following format:
where:
Variable Data is 1 to 5 ASCII digits (0-65535)
Variable Position is single ASCII digit (value is ignored)
DL5 Address is 1 to 3 ASCII digits (0-127)
For example, to send a value of 500 to a DL5 with an address of 99, the
following string would be sent:
Note: In Binary mode, variable data can be in the range 0 to 16,383. In
BCD mode, variable data must be in the range 0 to 3999. In Round Robin
and Numeric modes, variable data can be in the range of 0 to 65535.
ASCII ^V500\1\99^M
HEX 16 35 30 30 5C 31 5C 39 39 0D
CTRL-V
Variable
Data
\
Backslash
DL5
Address
Carriage
Return
Variable
Position
\
Backslash