Publication 2364E-5.10 - April 1998
R
EPLACEMENT
K
IT
I
NSTRUCTIONS
NRU™ Diode Bridge Assembly
Replacement (180 - 350A DC)
Contents In 180A DC and 350A DC NRUs, all 6 diodes (D1 - D6) and the both
the positive and negative heatsinks (HS1 - HS2) can be replaced
together as a single unit.
This publication describes how to replace the diode bridge assembly
in 180A DC and 350A DC non-regenerative, front-end units (NRU).
What This Kit Contains Using the table below, verify that you have received the appropriate
items in your kit:
Other Items Needed Before you begin, be sure you also have the following:
Whatever tool(s) you will need to:
Remove and connect line fuses and AC busbars
Disconnect and connect wires
Remove, loosen, and/or tighten bolts
Torque bolts
Documentation:
Your drive system schematics
Publication 2364E-5.01, Non-Regenerative DC Bus Sup-
ply (NRU) User Manual
For this part: You should receive this quantity:
diode bridge assembly 1
Zobrazit stránku 0
1 2 3 4 5 6 7 8

Shrnutí obsahu

Strany 1 - Replacement (180 - 350A DC)

Publication 2364E-5.10 - April 1998REPLACEMENT KIT INSTRUCTIONSNRU™ Diode Bridge Assembly Replacement (180 - 350A DC)Contents In 180A DC and 350A DC

Strany 2

2 NRU™ Diode Bridge Assembly Replacement (180 - 350A DC) Publication 2364E-5.10 - April 1998Safety Precautions The following general precautions appl

Strany 3 - Assembly

NRU™ Diode Bridge Assembly Replacement (180 - 350A DC) 3 Publication 2364E-5.10 - April 1998Removing the Diode Bridge Assembly This section

Strany 4 - Figure 4

4 NRU™ Diode Bridge Assembly Replacement (180 - 350A DC) Publication 2364E-5.10 - April 19983. Disconnect the wire between suppressor diode D11 at th

Strany 5 - Figure 5

NRU™ Diode Bridge Assembly Replacement (180 - 350A DC) 5 Publication 2364E-5.10 - April 19987. Loosen, but do not remove, the 2 lower bolts

Strany 6 - Installing the Diode Bridge

6 NRU™ Diode Bridge Assembly Replacement (180 - 350A DC) Publication 2364E-5.10 - April 1998Figure 6Power Bridge Without AC Busbars and Line FusesIns

Strany 7

NRU™ Diode Bridge Assembly Replacement (180 - 350A DC) 7 Publication 2364E-5.10 - April 19989. Reconnect both of the "Heatsink-Over-Tem

Strany 8 - P/N 173345

NRU is a trademark of Rockwell International or its subsidiaries.Lexan is a trademark of General Electric Corp.Publication 2364E-5.10 - April 1998Supe