NOTE: New settings to HIM parameters are implemented immediately.
Resetting the HIM is not required for new values to take effect.
12 [Ref Scaling]
Enables or disables scaling the Reference to a user-defined value.
When Parameter 12 - [Ref Scaling] is set to “1” (Enabled), use HIM
Parameters 13…22 to scale the Reference.
Default: 0 = Disabled
Values: 0 = Disabled
1 = Enabled
Type: Read/Write
13 [Ref Max Value]
Sets the user-defined value to be displayed when the drive is running
at 60 Hz.
Default: 600
Minimum: 100
Maximum: 65535
Type: Read/Write
14 [Ref Dec Position]
Sets the number of digits to be displayed to the right of the decimal
point for the Reference.
Default: 1
Minimum: 0
Maximum: 3
Type: Read/Write
15
16
17
18
19
20
21
22
[Ref Units Char 1]
[Ref Units Char 2]
[Ref Units Char 3]
[Ref Units Char 4]
[Ref Units Char 5]
[Ref Units Char 6]
[Ref Units Char 7]
[Ref Units Char 8]
Selects up to 8 characters (from the ISO 8859-1 character set) to use
for the Reference units on the Process Display.
Parameters 15…22 can also be configured using the “Edit Ref Text”
selection in the HIM Setup tab.
Default: 72 (“H”)
Default: 122 (“z”)
Default: 32 (blank - no character)
Default: 32 (blank - no character)
Default: 32 (blank - no character)
Default: 32 (blank - no character)
Default: 32 (blank - no character)
Default: 32 (blank - no character)
Minimum: 32
Maximum: 255
Type: Read/Write
23 [Fault Dspy Type]
Selects the type of display flash to be shown when a drive or
peripheral fault is detected.
Default: 0 = Flash Bklite
Values: 0 = Flash Bklite
1 = Flash None
Type: Read/Write
24 [Alarm Dspy Type]
Selects the type of display flash to be shown when a drive alarm is
detected.
Default: 1 = Flash None
Values: 0 = Flash Bklite
1 = Flash None
Type: Read/Write
Parameter
No. Name and Description Details
www.rockwellautomation.com
Americas: Rockwell Automation, 1201 South Second Street, Milwaukee, WI 53204-2496 USA, Tel: (1) 414.382.2000, Fax: (1) 414.382.4444
Europe/Middle East/Africa: Rockwell Automation, Vorstlaan/Boulevard du Souverain 36, 1170 Brussels, Belgium, Tel: (32) 2 663 0600, Fax: (32) 2 663 0640
Asia Pacific: Rockwell Automation, Level 14, Core F, Cyberport 3, 100 Cyberport Road, Hong Kong, Tel: (852) 2887 4788, Fax: (852) 2508 1846
Power, Control and Information Solutions Headquarters
U.S. Allen-Bradley Drives Technical Support
Tel: (1) 262.512.8176, Fax: (1) 262.512.2222, Email: support@drives.ra.rockwell.com, Online: www.ab.com/support/abdrives
Publication 22HIM-QR001F – September 2009
Supersedes 22HIM-QR001E-EN-P – April 2005 Copyright © 2009 Rockwell Automation, Inc. All rights reserved. Printed in USA.
Zobrazit stránku 3
1 2 3 4

Komentáře k této Příručce

Žádné komentáře