Strany 1 - DeviceNet

DeviceNet Adapter22-COMM-DFRN 1.xxxUser Manual

Strany 2 - Important User Information

P-2 About This ManualThe following conventions are used throughout this manual:• Parameter names are shown in the following format Parameter xx - [*].

Strany 3 - Summary of Changes

8-6 TroubleshootingThe adapter maintains an event queue that reports the history of its actions. You can view the event queue using DriveExplorer (3.0

Strany 4 - S-ii Summary of Changes

Troubleshooting 8-7EventsMany events in the Event queue occur under normal operation. If you encounter unexpected communications problems, the events

Strany 5 - Table of Contents

8-8 TroubleshootingNotes:

Strany 6 - Appendix A Specifications

Appendix ASpecificationsThis chapter present the specifications for the adapter.Topic Page Topic PageCommunications A-1 Environmental A-2Electrical A-

Strany 7 - Appendix C DeviceNet Objects

A-2 SpecificationsEnvironmentalTemperatureOperatingStorage-10 to +50 °C (14 to 149 °F)-40 to +85 °C (-40 to +185 °F)Relative Humidity -5 to 95% non-co

Strany 8

Appendix BAdapter ParametersAppendix B provides information about the DeviceNet adapter parameters. The parameters in the adapter are numbered consecu

Strany 9 - About This Manual

B-2 Adapter Parameters04 [DN Rate Cfg]Sets the DeviceNet data rate after a reset or power cycle.This setting is used when all of the adapter DIP switc

Strany 10 - Rockwell Automation Support

Adapter Parameters B-309 [DN Act Cfg]Displays the source from which the adapter node address and data rate are taken. This will either be switches or

Strany 11 - Getting Started

B-4 Adapter Parameters15 [DSI I/O Cfg]Sets the configuration of the Drives that are active in the Multi-Drive mode. Identifies the connections that wo

Strany 12 - Features

Appendix CDeviceNet ObjectsAppendix C presents information about the DeviceNet objects that can be accessed using Explicit Messages. For information o

Strany 13 - Required Equipment

Chapter 1Getting StartedThe 22-COMM-D DeviceNet adapter is a communication option intended for installation into a PowerFlex 40 drive. It can also be

Strany 14 - Safety Precautions

C-2 DeviceNet ObjectsClass CodeInstances (Single-Drive Mode)The number of instances is fixed at three and is as shown below:Instances (Multi-Drive Mod

Strany 15 - Quick Start

DeviceNet Objects C-3Instance AttributesServicesIdentity Object (Continued)Attribute IDAccess RuleName Data Type Description1 Get Vendor ID UINT 1 = A

Strany 16 - Modes of Operation

C-4 DeviceNet ObjectsClass CodeInstancesInstance AttributesRefer to the DeviceNet Specification for more information.Connection ObjectHexadecimal Deci

Strany 17 - Installing the Adapter

DeviceNet Objects C-5Instance Attributes (Continued)Refer to the DeviceNet Specification for more information.ServicesConnection Object (Continued)Att

Strany 18 - Figure 2.2, and Figure 2.3)

C-6 DeviceNet ObjectsClass CodeInstancesThe number of instances is fixed at thirteen and is as shown below:If a drive is not present, the Data instanc

Strany 19

DeviceNet Objects C-7Class AttributesNot supported.Instance AttributesImportant: Setting a register object attribute can only be accomplished through

Strany 20

C-8 DeviceNet ObjectsClass CodeInstances (Single-Drive Mode)The number of instances is as shown below:Instances (Multi-Drive Mode)The number of instan

Strany 21 - ➌ DeviceNet cable

DeviceNet Objects C-9Instance AttributesParameter Object (Continued)Attribute IDAccess RuleName Data Type Description1(1)(1)Access rule is defined in

Strany 22 - Adapter Mounted

C-10 DeviceNet ObjectsServicesParameter Object (Continued)Service Code Implemented for: Service NameClass Instance0x01 No Ye s Get_Attribute_All0x05 Y

Strany 23 - Applying Power

DeviceNet Objects C-11Class CodeInstances (Single-Drive Mode)The number of instances depends on the number of groups in the drive. A group of adapter

Strany 24 - 2-8 Installing the Adapter

1-2 Getting StartedThe DeviceNet adapter features the following:• The adapter is mounted in the PowerFlex 40 drive. It receives the required power fro

Strany 25 - Configuring the Adapter

C-12 DeviceNet ObjectsInstance AttributesServicesParameter Group Object (Continued)Attribute IDAccess RuleName Data TypeDescription1 Get Group Name St

Strany 26 - Using the HIM

DeviceNet Objects C-13Class CodeInstancesNot supportedClass AttributesNot supported.Instance AttributesNot supported.ServicesPCCC ObjectHexadecimal De

Strany 27 - Using RSNetWorx for DeviceNet

C-14 DeviceNet ObjectsMessage Structure for Execute_PCCCMessage Structure for Execute_Local_PCCCPCCC Object (Continued)Request ResponseName DataTypeDe

Strany 28

Appendix DLogic Command/Status WordsAppendix D provides the definitions of the Logic Command/Logic Status words that are used for some products that c

Strany 29 - To create an EDS file

D-2 Logic Command/Status WordsLogic Status WordPowerFlex 4 and PowerFlex 40 DrivesLogic Bits15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Status Descriptionx

Strany 30 - To access and edit parameters

GlossaryA AdapterDevices such as drives, controllers, and computers usually require an adapter to provide a communication interface between them and a

Strany 31 - Setting the Data Rate

Glossary-2ControllerA controller, also called programmable logic controller, is a solid-state control system that has a user-programmable memory for s

Strany 32 - Setting the I/O Configuration

Glossary-3DeviceNet NetworkA DeviceNet network uses a producer/consumer Controller Area Network (CAN) to connect devices (for example, controllers, dr

Strany 33 - VAL UE LIMITS SEL !

Glossary-4DriveTools SoftwareA software suite designed for Microsoft Windows 95, Windows 98, and Windows NT (4.0 or greater) operating systems. This s

Strany 34 - Setting a Fault Action

Glossary-5Flash UpdateThe process of updating firmware in the adapter. The adapter can be flash updated using the X-Modem protocol and a 1203-SSS Smar

Strany 35 - Resetting the Adapter

Getting Started 1-3The DeviceNet adapter is compatible with Allen-Bradley PowerFlex drives and other products that support an internal DSI adapter. At

Strany 36 - 3-12 Configuring the Adapter

Glossary-6N Node AddressA DeviceNet network can have as many as 64 devices connected to it. Each device on the network must have a unique node address

Strany 37 - Configuring the Scanner

Glossary-7Producer/Consumer NetworkOn producer/consumer networks, packets are identified by content rather than an explicit destination. If a node nee

Strany 38 - Setting Up the Scan List

Glossary-8U UCMM (UnConnected Message Manager)UCMM provides a method to create connections between DeviceNet devices.Z Zero DataWhen communications ar

Strany 39 - Configuring the Scanner 4-3

IndexNumerics10-pin linear plug, 2-45-pin linear plug, 2-4Aadapteradding to the scan list, 4-2applying power, 2-7commissioning, 2-1compatible products

Strany 40

Index-2COS, refer to Change of StateCOS/Cyc Interval parameter, B-3Cyclicconfiguring a scanner for, 4-4configuring an adapter for, 3-8definition, G-2D

Strany 41 - Mapping the Input I/O

Index-3Ffault actionconfiguring an adapter, 3-10definition, G-4fault configurationconfiguring an adapter for, 3-10definition, G-4faulted node recovery

Strany 42 - Mapping the Output I/O

Index-4mechanical dimensions, A-1messages, refer to Explicit MessagesMOD status indicatorlocating, 8-1troubleshooting with, 8-3modes of operation, 1-6

Strany 43 - Saving the Configuration

Index-5Rreference/feedbackdefinition, G-7in I/O image, 5-2, 7-4using, 5-3Register object, C-6regulatory compliance, A-1related documentation, P-1Reset

Strany 46 - Using Logic Command/Status

1-4 Getting StartedPlease read the following safety precautions carefully:Safety Precautions!ATTENTION: Risk of injury or death exists. The PowerFlex

Strany 47 - Example Ladder Logic Programs

Publication 22COMM-UM003A-EN-P – January, 2003 P/N 308269-P01Copyright 2003 Rockwell International Corporation. All rights reserved. Printed in USA.

Strany 48 - ControlLogix Example

Getting Started 1-5This section is designed to help experienced users start using the DeviceNet adapter. If you are unsure how to complete a step, ref

Strany 49 - Using I/O Messaging 5-5

1-6 Getting StartedThe adapter uses three status indicators to report its operating status. They can be viewed through the drive cover. See Figure 1.2

Strany 50 - Figure 6.6

Chapter 2Installing the AdapterChapter 2 provides instructions for installing the adapter in a PowerFlex 40 drive.Before installing the DeviceNet adap

Strany 51 - Using I/O Messaging 5-7

2-2 Installing the Adapter1. Set the adapter node address and data rate switches (see Figure 2.1, Figure 2.2, and Figure 2.3).Figure 2.1 Setting Nod

Strany 52 - Figure 6.7

Installing the Adapter 2-3If all switches are in the CLOSED position (all 0’s), then the Node Address and Data Rate are determined by parameter settin

Strany 53 - Using I/O Messaging 5-9

Important User InformationSolid state equipment has operational characteristics differing from those of electromechanical equipment. “Safety Guideline

Strany 54 - 5-10 Using I/O Messaging

2-4 Installing the Adapter1. Remove power from the drive.2. Use static control precautions.3. Remove the drive cover.4. Connect a DeviceNet cable to t

Strany 55 - Figure 6.8

Installing the Adapter 2-51. Remove power from the drive.2. Use static control precautions.3. Mount the adapter on the cover, using the screw on the a

Strany 56 - 5-12 Using I/O Messaging

2-6 Installing the AdapterFigure 2.6 Mounting the Adapter PowerFlex 40 DriveB and C Frames (cover removed)Adapter Mounted on Back of Cover

Strany 57 - Using Explicit Messaging

Installing the Adapter 2-71. Reinstall the cover on the drive. The status indicators can be viewed on the front of the drive after power has been appl

Strany 58

2-8 Installing the AdapterNotes:

Strany 59 - Using Explicit Messaging 6-3

Chapter 3Configuring the AdapterChapter 3 provides instructions and information for setting the parameters in the adapter.For a list of parameters, re

Strany 60

3-2 Configuring the AdapterThe PowerFlex 4-Class HIM (Human Interface Module) can be used to access parameters in the adapter (see basic steps shown b

Strany 61 - Using Explicit Messaging 6-5

Configuring the Adapter 3-3RSNetWorx for DeviceNet is a Rockwell Software application that can be used to set up DeviceNet networks and configure conn

Strany 62 - Message request

3-4 Configuring the AdapterTo go online with RSNetWorx for DeviceNetYou can view the devices on a DeviceNet network by going online. A device may appe

Strany 63

Configuring the Adapter 3-5To create an EDS fileIf the adapter and drive appear as an unrecognized device, create an EDS file for it.Figure 3.3 EDS

Strany 64

Summary of ChangesThis is the first release of the DeviceNet adapter FRN 1.xxx.

Strany 65 - Using Explicit Messaging 6-9

3-6 Configuring the AdapterTo access and edit parametersParameters in the drive and adapter can be edited with RSNetWorx. The adapter parameters are a

Strany 66 - Figure 5.3

Configuring the Adapter 3-7The value of Parameter 02 - [DN Addr Cfg] determines the node address if all of the adapter DIP switches are in the CLOSED

Strany 67 - PLC-5 Example

3-8 Configuring the AdapterThe I/O configuration determines the number of drives that will be represented on the network as one node by the adapter. I

Strany 68 - Ladder Logic Program

Configuring the Adapter 3-9Cyclic and Polled data exchanges are configured in the scanner, so you only need to set the I/O configuration in the adapte

Strany 69 - SLC Example

3-10 Configuring the AdapterBy default, when communications are disrupted (for example, a cable is disconnected) or the scanner is idle, the drive res

Strany 70

Configuring the Adapter 3-11To set the fault configuration parametersIf you set Parameter 07 - [Comm Flt Action] or 08 - [Idle Flt Action] to the “Sen

Strany 71 - Figure 5.6

3-12 Configuring the AdapterThe following parameters provide information about how the adapter is configured. You can view these parameters at any tim

Strany 72 - 6-16 Using Explicit Messaging

Chapter 4Configuring the ScannerChapter 4 provides instructions on how to configure a scanner to communicate with the adapter and connected PowerFlex

Strany 73 - Using Multi-Drive Mode

4-2 Configuring the ScannerFor the scanner to communicate with a drive, the scanner must be configured and the drive’s node number must be added to it

Strany 74

Configuring the Scanner 4-36. Under Available Devices, select the drive, and then click > (Right Arrow) to add it to the scanlist.Figure 4.3 Scan

Strany 75

S-ii Summary of Changes

Strany 76

4-4 Configuring the ScannerFigure 4.4 Edit I/O Parameters Dialog Box8. Select the type(s) of data exchange (Polled, Change of State, and /or Cyclic)

Strany 77

Configuring the Scanner 4-511. Click OK. If you changed any settings, a Scanner Applet asks if it is OK to unmap the I/O. Click Ye s to continue. The

Strany 78

4-6 Configuring the ScannerIf you selected the Automap on Add box in the Scanlist page (Figure 4.3), RSNetWorx has already mapped the I/O. If it is no

Strany 79

Configuring the Scanner 4-7If you selected the Automap on Add box in the Scanlist page (Figure 4.3), RSNetWorx has already mapped the I/O. If it is no

Strany 80 - Main Routine

4-8 Configuring the Scanner

Strany 81 - Using Multi-Drive Mode 7-9

Chapter 5Using I/O MessagingChapter 5 provides information and examples that explain how to useI/O Messaging to control a PowerFlex 40 drive.On Device

Strany 82

5-2 Using I/O MessagingThe DeviceNet specification requires that the terms input and output be defined from the scanner’s point of view. Therefore, Ou

Strany 83 - Using Multi-Drive Mode 7-11

Using I/O Messaging 5-3When enabled, Reference/Feedback begins at word 1 in the I/O image. The Reference (16 bits) is produced by the controller and c

Strany 84 - 7-12 Using Multi-Drive Mode

5-4 Using I/O MessagingLogic Command/Status WordsThese examples use the Logic Command word and Logic Status word for PowerFlex 40 drives. Refer to App

Strany 85 - Using Multi-Drive Mode 7-13

Using I/O Messaging 5-5Figure 5.3 Example ControlLogix Ladder Logic ProgramControlLogix example program with a PowerFlex 40 at node address 1.This r

Strany 86 - 7-14 Using Multi-Drive Mode

Table of ContentsPreface About This Manual Related Documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P-1Conventions Used in thi

Strany 87 - Using Multi-Drive Mode 7-15

5-6 Using I/O MessagingFor the explicit message portion of this ladder example program, see Figure 6.6.Figure 5.3 Example ControlLogix Ladder Logic

Strany 88 - 7-16 Using Multi-Drive Mode

Using I/O Messaging 5-7Figure 5.4 Control File for Block TransfersPLC-5 ExampleEN ST DN ER CO EW NR TO RW RLEN DLEN FILE ELEM R G SBT20:0 0 0 0 0 0

Strany 89 - Using Multi-Drive Mode 7-17

5-8 Using I/O MessagingFor the explicit message portion of this ladder example program, see Figure 6.7.Figure 5.5 Example PLC-5 Ladder Logic Program

Strany 90 - 7-18 Using Multi-Drive Mode

Using I/O Messaging 5-9SLC ExampleFigure 5.6 Example SLC Ladder Logic ProgramSLC 5/03 example program with a PowerFlex 40 at DeviceNet node address

Strany 91 - Using Multi-Drive Mode 7-19

5-10 Using I/O MessagingFigure 5.6 Example SLC Ladder Logic Program (Continued)0006B3:04Node 1ForwardCommand O:121 1747-SDNNode 1Logic CommandR

Strany 92

Using I/O Messaging 5-11For the explicit message portion of this ladder example program, see Figure 6.8.Figure 5.6 Example SLC Ladder Logic Program

Strany 93

5-12 Using I/O Messaging

Strany 94 - Additional Information

Chapter 6Using Explicit MessagingChapter 6 provides information and examples that explain how to use Explicit Messaging to monitor and configure the a

Strany 95 - Troubleshooting

6-2 Using Explicit MessagingExplicit Messages for a ControlLogix ControllerControlLogix scanners accommodate both downloading Explicit Message Request

Strany 96 - PORT Status Indicator

Using Explicit Messaging 6-3The following table identifies the number of Explicit Messages that can be executed at a time. ControlLogix Message Reques

Strany 97 - MOD Status Indicator

ii Table of ContentsChapter 5 Using I/O MessagingAbout I/O Messaging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1Understanding t

Strany 98 - Net A Status Indicator

6-4 Using Explicit MessagingExplicit Messages for a PLC or SLC ControllerTransaction blocks in PLC and SLC scanners accommodate both downloading Expli

Strany 99 - (version 3.01 or higher)

Using Explicit Messaging 6-5The following table identifies the number of transaction blocks within a scanner that are reserved for Explicit Messaging.

Strany 100 - Viewing and Clearing Events

6-6 Using Explicit MessagingPLC / SLC Explicit Message ResponsesRefer to Page 6-5 for a description of the words in a PLC/SLC Explicit Message request

Strany 101 - Troubleshooting 8-7

Using Explicit Messaging 6-7There are five basic events in the Explicit Messaging process. The details of each step will vary depending on the control

Strany 102 - 8-8 Troubleshooting

6-8 Using Explicit MessagingData Format for a Read and Write ParameterThe data in this example is for a PowerFlex drive at node address 1.Refer to For

Strany 103 - Specifications

Using Explicit Messaging 6-9Figure 6.5 Tags for the Example Explicit Messaging ProgramConfiguration Example Value Description Refer to . . .Service

Strany 104 - Regulatory Compliance

6-10 Using Explicit MessagingFigure 6.6 Example ControlLogix Ladder Logic ProgramFor the I/O message portion of this ladder example program, see Fig

Strany 105 - Adapter Parameters

Using Explicit Messaging 6-11Data Format for a Read and Write ParameterThe data in this example is for a PowerFlex drive at node address 1.Refer to Fo

Strany 106 - B-2 Adapter Parameters

6-12 Using Explicit MessagingLadder Logic ProgramFigure 6.7 Example PLC-5 Ladder Logic ProgramFor the I/O message portion of this ladder example pro

Strany 107 - Adapter Parameters B-3

Using Explicit Messaging 6-13Data Format for a Read and Write ParameterThe data in this example is for a PowerFlex drive at node address 1.Refer to Fo

Strany 108 - B-4 Adapter Parameters

Table of Contents iiiAppendix B Adapter ParametersAbout Parameter Numbers. . . . . . . . . . . . . . . . . . . . . . . . . . . B-1Parameter List . .

Strany 109 - DeviceNet Objects

6-14 Using Explicit MessagingResponse Data for Write to Drive Parameter 101ProgramImportant: To originate a scanner transaction, use a copy operation

Strany 110 - Identity Object

Using Explicit Messaging 6-15Figure 6.8 Example SLC Ladder Logic ProgramFor the I/O message portion of this ladder example program, see Figure 5.6.E

Strany 111 - Identity Object (Continued)

6-16 Using Explicit MessagingNotes:

Strany 112 - Connection Object

Chapter 7Using Multi-Drive ModeChapter 7 provides information and a ControlLogix ladder example to explain how to use Multi-Drive mode.Single mode is

Strany 113 - Connection Object (Continued)

7-2 Using Multi-Drive ModeFigure 7.2 Multi-Drive Mode Example for NetworkBenefits of Multi-Drive mode include:• Lower hardware costs. Only one 22-CO

Strany 114 - Register Object

Using Multi-Drive Mode 7-3• Automatic Device Replacement (ADR) cannot be used with any of the drives.• The RSNetWorx Parameter editor cannot be used.•

Strany 115 - Register Object (Continued)

7-4 Using Multi-Drive ModeThe DeviceNet specification requires that the terms input and output be defined from the scanner’s point of view. Therefore,

Strany 116 - Parameter Object

Using Multi-Drive Mode 7-5The following parameters must be set in the daisy-chained drives:Note that the RS-485 network is fixed at 19.2K baud, 8 data

Strany 117 - Parameter Object (Continued)

7-6 Using Multi-Drive ModeThe example ladder logic program demonstrates using Multi-Drive mode with five drives. See Figure 7.2 for a system layout di

Strany 118

Using Multi-Drive Mode 7-7Drive Settings for the Example ProgramThe following common Tags are used:The following Tags are used for Drive 0:ParameterVa

Strany 120 - (Continued)

7-8 Using Multi-Drive ModeThe same type of Tags are also used for Drive 1 through Drive 4.Main RoutineThe Main Routine tells the 1756-DNB scanner to r

Strany 121 - PCCC Object

Using Multi-Drive Mode 7-9Figure 7.6 Main RoutineThis rung enables the scanner (changes the scanner to RUN mode).0 Local:3:O.CommandRegister.RunThis

Strany 122 - PCCC Object (Continued)

7-10 Using Multi-Drive ModeDrive 0 - Drive 4 Control RoutinesThe Drive Control routines provide status information (Logic Status and Feedback), contro

Strany 123 - Logic Command/Status Words

Using Multi-Drive Mode 7-11Figure 7.7 Drive 0 Control RoutineDrive 0 Control Subroutine0 DriveInputImage[0].0 Drive0StatusReadyDrive 0 Control Subro

Strany 124 - Logic Status Word

7-12 Using Multi-Drive ModeFigure 7.7 Drive 0 Control Routine (Continued)Explicit Messaging Example13 PerformParameterRead0ENDNERType - CIP GenericM

Strany 125 - Glossary

Using Multi-Drive Mode 7-13Figure 7.8 Drive 1 Control RoutineDrive 1 Control Subroutine0 DriveInputImage[2].0 Drive1StatusReadyDrive 1 Control Subro

Strany 126 - D Data Rate

7-14 Using Multi-Drive ModeFigure 7.8 Drive 1 Control Routine (Continued)Explicit Messaging Example13 PerformParameterRead1ENDNERType - CIP GenericM

Strany 127

Using Multi-Drive Mode 7-15Figure 7.9 Drive 2 Control RoutineDrive 2 Control Subroutine0 DriveInputImage[4].0 Drive2StatusReadyDrive 2 Control Subro

Strany 128 - F Fault Action

7-16 Using Multi-Drive ModeFigure 7.9 Drive 2 Control Routine (Continued)Explicit Messaging Example13PerformParameterRead2ENDNERType - CIP GenericMe

Strany 129 - L Logic Command/Logic Status

Using Multi-Drive Mode 7-17Figure 7.10 Drive 3 Control RoutineDrive 3 Control Subroutine0 DriveInputImage[6].0 Drive3StatusReadyDrive 3 Control Subr

Strany 130 - O Objects

PrefaceAbout This Manual Documentation can be obtained online at http://www.ab.com/manuals.Topic PageRelated Documentation P-1Conventions Used in this

Strany 131 - S Scanner

7-18 Using Multi-Drive ModeFigure 7.10 Drive 3 Control Routine (Continued)Explicit Messaging Example13 PerformParameterRead3ENDNERType - CIP Generic

Strany 132 - Z Zero Data

Using Multi-Drive Mode 7-19Figure 7.11 Drive 4 Control RoutineDrive 4 Control Subroutine0 DriveInputImage[8].0 Drive4StatusReadyDrive 4 Control Subr

Strany 133 - Numerics

7-20 Using Multi-Drive ModeParameter addressing for Explicit messaging is different in Multi-Drive than with Single mode. In Single mode, the Instance

Strany 134

Using Multi-Drive Mode 7-21Drive 0 Explicit Message ExampleThe Explicit message examples in the ControlLogix example program perform a read (Get_Attri

Strany 135

7-22 Using Multi-Drive ModeThe Class Code is “ f ” for the Parameter Object and the Instance Attribute is “1” to select retrieving the parameter value

Strany 136

Chapter 8TroubleshootingChapter 8 contains troubleshooting information.The DeviceNet adapter has three status indicators. They can be viewed on the ad

Strany 137

8-2 TroubleshootingPORT Status IndicatorStatus Cause Corrective ActionOff The adapter is not powered or is not connected properly to the drive.• Secur

Strany 138

Troubleshooting 8-3MOD Status IndicatorStatus Cause Corrective ActionOff The adapter is not powered. • Securely connect the adapter to the drive using

Strany 139

8-4 TroubleshootingThe following diagnostic items can be accessed using DriveExplorer (version 3.01 or higher).Net A Status IndicatorStatus Cause Corr

Strany 140

Troubleshooting 8-5The following diagnostic items can be accessed using DriveExplorer (version 3.01 or higher).Module Diagnostic Items in Multi-Drive