5-6 Troubleshooting
7–9 Reserved
DSI Events
10 Slave Detected The adapter detected that the slave has been connected.
11 Slave Removed The adapter detected that the slave has been disconnected.
12 Slave Logon The adapter has established communications with the slave.
13 Slave Timeout The adapter has lost communications with the slave.
14 Slave Brand Flt The slave brand is different than the adapter.
15 Host 0 Logon The adapter has established communications with the drive.
16-19 Reserved
20 Host 0 Timeout The adapter has lost communications with the drive.
21-24 Reserved
25 Host 0 Brand Flt The drive is not an Allen-Bradley brand drive.
26–39 Reserved
Network Events
40 Net Link Up The network link is established.
41 Net Link Down The network link is lost.
42 Dup Net Addr The adapter detected that another device is using its network
address. In this case, the adapter will not participate in any
network activity.
43 Net Open An I/O connection from the network to the adapter was opened.
44 Net Close An I/O connection from the network to the adapter was closed.
45 Net Timeout An I/O connection from the network to the adapter has timed
out.
46 Net Comm Flt The adapter has performed the “Comm Flt” action specified by
the user.
47 Net Idle Flt The adapter has performed the “Idle Flt” action specified by the
user.
48 PCCC IO Open The adapter has begun receiving PCCC Control messages (the
PCCC Control Timeout was previously set to a non-zero value).
49 PCCC IO Close The device sending PCCC Control messages to the adapter
has set the PCCC Control Timeout to a value of zero.
50 PCCC IO Time
Flt
The adapter has not received a PCCC Control message for
longer than the PCCC Control Timeout.
51 Net Sent Reset The adapter received a reset from the network.
52 Msg Ctrl Open The adapter has begun receiving Client-Server Control
messages (the Client-Server Control Timeout was previously
set to a non-zero value).
53 Msg Ctrl Close The device sending Client-Server Control messages to the
adapter has set the Client-Server Control Timeout to a value of
zero.
54 Msg Ctrl
Timeout
The adapter has not received a Client-Server Control message
for longer than the established timeout period.