2 PowerFlex® DC Drive - Frame A SCR Modules for Drives with Bus Bars
What You Need to Do
The SCR modules are located on the heat sink of the drive chassis, below all
circuit boards and components. To install the SCR modules:
Step 1: Remove power from the drive
Step 2: Remove the protective covers
Step 3: Remove the Control EMI shield and Control board
Step 4: Remove the Pulse Transformer and Switching Power Supply
boards
Step 5: Remove the bus bars
Step 6: Remove the existing SCR modules
Step 7: Install the new SCR modules
Step 8: Install the bus bars
Step 9: Install the Pulse Transformer and Switching Power Supply
boards
Step 10: Install the Control EMI Shield and Control board
Step 11: Replace the protective covers and document the change
Step 1: Remove Power
from the Drive
1. Remove and lock-out all incoming power to the drive.
ATTENTION: Remove power before making or breaking cable
connections. When you remove or insert a cable connector with
power applied, an electrical arc may occur. An electrical arc can
cause personal injury or property damage by:
sending an erroneous signal to your system’s field devices,
causing unintended machine motion
causing an explosion in a hazardous environment
Electrical arcing causes excessive wear to contacts on both the
module and its mating connector. Worn contacts may create
electrical resistance.
L1 L2 L3