Par Parameter Name Factory Default Programmed Value Par Parameter Name Factory Default Programmed Value
101 Preset Speed 1 5.0 Hz 195 MOP Rate 1.0 Hz/s
102 Preset Speed 2 10.0 Hz 196 Param Access Lvl Basic
103 Preset Speed 3 20.0 Hz 197 Reset To Defalts Ready
104 Preset Speed 4 30.0 Hz 198 Load Frm Usr Set Ready
105 Preset Speed 5 40.0 Hz 199 Save To User Set Ready
106 Preset Speed 6 50.0 Hz 200 Reset Meters Ready
107 Preset Speed 7 60.0 Hz 201 Language Not Selected
117 Trim In Select Analog In 2 202 Voltage Class Based on Drive Cat. No.
118 Trim Out Select xxxxxxxxxxxxxx00 203 Drive Checksum Read Only
119 Trim Hi 60.0 Hz 209 Drive Status 1 Read Only
120 Trim Lo 0.0 Hz 210 Drive Status 2 Read Only
121 Slip RPM @ FLA
Based on
[Motor NP RPM] 211 Drive Alarm 1 Read Only
122 Slip Comp Gain 40.0 212 Drive Alarm 2 Read Only
123 Slip RPM Meter Read Only 213 Speed Ref Source Read Only
124 PI Configuration xxxxxxxxxx000000 214 Start Inhibits Read Only
125 PI Control xxxxxxxxxxxxx000 215 Last Stop Source Read Only
126 PI Reference Sel PI Setpoint 216 Dig In Status Read Only
127 PI Setpoint 50.00% 217 Dig Out Status Read Only
128 PI Feedback Sel Analog In 2 218 Drive Temp Read Only
129 PI Integral Time 2.00 Secs 219 Drive OL Count Read Only
130 PI Prop Gain 1.00 220 Motor OL Count Read Only
131 PI Lower Limit -[Maximum Freq] 224 Fault Frequency Read Only
132 PI Upper Limit +[Maximum Freq] 225 Fault Amps Read Only
133 PI Preload 0.0 Hz 226 Fault Bus Volts Read Only
134 PI Status Read Only 227 Status 1 @ Fault Read Only
135 PI Ref Meter Read Only 228 Status 2 @ Fault Read Only
136 PI Fdback Meter Read Only 229 Alarm 1 @ Fault Read Only
137 PI Error Meter Read Only 230 Alarm 2 @ Fault Read Only
138 PI Output Meter Read Only 234 Testpoint 1 Sel 499
140 Accel Time 1 10.0 Secs 235 Testpoint 1 Data Read Only
141 Accel Time 2 10.0 Secs 236 Testpoint 2 Sel 499
142 Decel Time 1 10.0 Secs 237 Testpoint 2 Data Read Only
143 Decel Time 2 10.0 Secs 238 Fault Config 1 xxxxxxxxx1001x10
146 S-Curve % 0% 240 Fault Clear Ready
147 Current Lmt Sel Cur Lim Val 241 Fault Clear Mode Enabled
148 Current Lmt Val [Rated Amps] x 1.5 242 Power Up Marker Read Only
149 Current Lmt Gain 250 243 Fault 1 Code Read Only
150 Drive OL Mode Both-PWM 1st 244 Fault 1 Time Read Only
151 PWM Frequency 4 kHz 245 Fault 2 Code Read Only
155 Stop Mode A Ramp 246 Fault 2 Time Read Only
156 Stop Mode B Coast 247 Fault 3 Code Read Only
157 DC Brk Lvl Sel DC Brake Lvl 248 Fault 3 Time Read Only
158 DC Brake Level [Rated Amps] 249 Fault 4 Code Read Only
159 DC Brake Time 0.0 sec 250 Fault 4 Time Read Only
160 Bus Reg Ki 450 259 Alarm Config 1 xxxxxx111x111111
161 Bus Reg Mode A Adjust Freq 270 DPI Baud Rate 125 kbps
162 Bus Reg Mode B Both-Frq 1st 271 Drive Logic Rslt Read Only
163 DB Resistor Type Internal Res 272 Drive Ref Rslt Read Only
168 Start At PowerUp Disabled 273 Drive Ramp Rslt Read Only
169 Flying Start En Disabled 276 Logic Mask xxxxxxxxxx1x1111
170 Flying StartGain 4000 277 Start Mask xxxxxxxxxx1x1111
174 Auto Rstrt Tries 0 278 Jog Mask xxxxxxxxxx1x1111
175 Auto Rstrt Delay 1.0 Secs 279 Direction Mask xxxxxxxxxx1x1111
184 Power Loss Mode Coast 280 Reference Mask xxxxxxxxxx1x1111
185 Power Loss Time 0.5 Secs 281 Accel Mask xxxxxxxxxx1x1111
190 Direction Mode Unipolar 282 Decel Mask xxxxxxxxxx1x1111
192 Save HIM Ref xxxxxxxxxxxxxxx1 283 Fault Clr Mask xxxxxxxxxx1x1111
193 Man Ref Preload Disabled 284 MOP Mask xxxxxxxxxx1x1111
194 Save MOP Ref xxxxxxxxxxxxxx00 285 Local Mask xxxxxxxxxx1x1111