Rockwell-automation 20-COMM-E PowerFlex EtherNet/IP Adapter Uživatelský manuál Strana 86

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 296
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 85
4-40 Configuring the I/O
20-COMM-E EtherNet/IP Adapter User Manual
Publication 20COMM-UM010G-EN-P
Creating RSLogix 500 Project, Version 7.00 or Later
To transmit (read and write) data between the controller and drive, you must
create message instructions that allocate data table addresses in the controller
for Logic Command/Status, Reference/Feedback, and Datalinks.
Select the Controller
1. Start RSLogix 500 software.
The RSLogix 500 window appears.
2. Select File > New to display the Select Processor Type screen.
3. Assign a name for the processor.
4. In the list, select the MicroLogix 1100 controller.
5. Choose the appropriate selections for the fields in the screen to match
your application.
6. Click OK.
The RSLogix 500 project window appears.
Zobrazit stránku 85
1 2 ... 81 82 83 84 85 86 87 88 89 90 91 ... 295 296

Komentáře k této Příručce

Žádné komentáře