19 12 Input/12 Output Discrete Embedded TTL I/O Module with Pulse Width Modulation and DeviceLogix
Publication 1799-IN008A-EN-P - July 2005
General Specifications (continued)
LED Indicators Board Status - red/green
Network Status - red/green
DeviceLogix Status - green
Input Point LED - yellow
Output Point LED - yellow
5V I/O supply - green
Approximate Dimensions
Millimeters (Inches)
165.1 mm x 88.9 mm x 3.53 mm
(6.5 in. x 3.5 in. x 0.14 in.)
Operational Temperature
IEC 60068-2-1 (Test Ad, Operating Cold),
IIEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20...70
o
C (14...158
o
F)
Storage Temperature
IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Un-packaged Non-operating Thermal Shock):
-40... 85
o
C (-40...185
o
F)
Relative Humidity IEC 60068-2-30 (Test Db, Un-packaged Non-operating Damp Heat):
5...95% non-condensing
Vibration IEC 60068-2-6 (Test Fc, Operating):
5g @ 10-500Hz
Operating Shock IEC 60068-2-27 (Test Ea, Unpackaged Shock):
30g
Non-Operating Shock IEC 60068-2-27 (Test Ea, Unpackaged Shock):
50g
Emissions CISPR 11:
Group 1, Class A
ESD Immunity IEC 61000-4-2:
8 kV indirect contact discharges
Radiated RF Immunity IEC 61000-4-3:
10V/m with 1kHz sine-wave 80%AM from 30MHz...2000 MHz
10V/m with 200Hz 50% Pulse 100%AM at 900 MHz
10V/m with 200Hz 50%Pulse 100% AM at 1890 MHz