FLEX I/O Isolated Output HART Analog Module 23
Publication
1794-IN120C-EN-P - April 2009
Status Indicator
The OK status indicator is bicolor, red, and green. The indicator
flashes green for these reasons:
• The module configuration word is zero (for example,
powerup reset condition).
• The 24V DC user power is off.
• The module is in Configuration mode.
The indicator displays red to indicate the module did not pass the
initial hardware test. Recycle power in response to this display.
After powerup, if the status indicator is not flashing green or solid
green, recycle module power to verify a proper reset of the bus
interface.
Specifications
FLEX I/O Isolated Output Analog Module - 1794-OF8IH
Attribute Value
Number of outputs 8 isolated
Module base Catalog numbers 1794-TB3, 1794-TB3S
Resolution 16 bits - unipolar
Current 0.305 µA/cnt unipolar
Data format
Engineering Units
(3)
Percent of Full Scale
RAW/Proportional Count
Update rate 10 ms
Output current terminal 4…20 mA (user configurable)
0…20 mA (user configurable)
Settling Time 70 ms, 0…99.9%
Load resistance 0 Ω… 750 Ω standard
Load reactance, max 10 µH
Komentáře k této Příručce