2–14 Installing Your Remote I/O Adapter Module
Publication 1794ĆUM009D-EN-P - April 2004
S1 Switch PositionRack Number
123456PLCĆ3PLCĆ5/250PLCĆ51747ĆSN
Rack 42 ON OFF ON ON ON OFF
Rack 43 OFF OFF ON ON ON OFF
Rack 44 ON ON OFF ON ON OFF
Rack 45 OFF ON OFF ON ON OFF
Rack 46 ON OFF OFF ON ON OFF
Rack 47 OFF OFF OFF ON ON OFF
Rack 50 ON ON ON OFF ON OFF
Rack 51 OFF ON ON OFF ON OFF
Rack 52 ON OFF ON OFF ON OFF
Rack 53 OFF OFF ON OFF ON OFF
Rack 54 ON ON OFF OFF ON OFF
Rack 55 OFF ON OFF OFF ON OFF
Rack 56 ON OFF OFF OFF ON OFF
Rack 57 OFF OFF OFF OFF ON OFF
Rack 60 ON ON ON ON OFF OFF
Rack 61 OFF ON ON ON OFF OFF
Rack 62 ON OFF ON ON OFF OFF
Rack 63 OFF OFF ON ON OFF OFF
Rack 64 ON ON OFF ON OFF OFF
Rack 65 OFF ON OFF ON OFF OFF
Rack 66 ON OFF OFF ON OFF OFF
Rack 67 OFF OFF OFF ON OFF OFF
Rack 70 ON ON ON OFF OFF OFF
Rack 71 OFF ON ON OFF OFF OFF
Rack 72 ON OFF ON OFF OFF OFF
Rack 73 OFF OFF ON OFF OFF OFF
Rack 74 ON ON OFF OFF OFF OFF
Rack 75 OFF ON OFF OFF OFF OFF
Rack 76 ON OFF OFF OFF OFF OFF
Not Valid OFF OFF OFF OFF OFF OFF
Rack address 77 is an illegal configuration.
PLCĆ5/11 processors can scan rack 03.
PLCĆ5/15 and PLCĆ5/20 processors can scan racks 01-03.
PLCĆ5/25 and PLCĆ5/30 processors can scan racks 01-07.
PLCĆ5/40 and PLCĆ5/40L processors can scan racks 01-17.
PLCĆ5/60 and PLCĆ5/60L processors can scan racks 01-27.
PLCĆ5/250 processors can scan racks 00-37.
PLCĆ3 processors can scan racks 00-76.
Note1-Whenusing a 1794ĆASB series C (or later) adapter module, rack addresses 40 to 76 are only available in Standard and
Standard-32 modes.