6 FLEX I/ODual Port EtherNet/IP Adapter Modules
Publication 1794-IN131A-EN-P - January 2012
Environmental Specifications
Certifications
Mounting Dimensions
The module has the following mounting dimensions.
Attribute Value
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0…55 °C (32…131 °F) 1794-AENTR
-25 …70 °C (-13…158 °F) – 1794-AENTRXT
Temperature,
surrounding air, max
55 °C (131 °F) – 1794-AENTR
70 °C (158 °F) – 1794-AENTRXT
Temperature,
nonoperating
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry
Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating
Thermal Shock):
-40…85 °C (-40…185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5 …95% non-condensing
Vibration IEC60068-2-6 (Test Fc, Operating):
5 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock):
30 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock):
50 g
Emissions CISPR 11:
Group 1, Class A
ESD immunity IEC 61000-4-2:
6 kV contact discharges
8 kV air discharges
Radiated RF immunity IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz
10/m with 1 kHz sine-wave 80% AM from
2000…2700 MHz
EFT/B immunity IEC 61000-4-4:
±4 kV at 5 kHz on power ports
±4 kV at 5 kHz on communication ports
Surge transient
immunity
IEC 61000-4-5:
±1 kV line-line (DM) and ±2 kV line-earth(CM) on
power ports
±2 kV line-earth(CM) on communication ports
Conducted RF immunity IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM from 150
kHz…80
MHz
Attribute
(when product is
marked
(1)
)
Value
c-UL-us UL Listed Industrial Control Equipment, certified for US and
Canada. See UL File E322657.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous
Locations, certified for U.S. and Canada. See UL File E334470.
CE European Union 2004/108/EC EMC Directive, compliant with:
EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:
AS/NZS CISPR 11; Industrial Emissions
Ex European Union 94/9/EC ATEX Directive, compliant with:
EN 60079-15; Potentially Explosive Atmospheres, Protection "n"
EN 60079-0; General Requirements
EN 60079-11; Explosive Atmospheres, Protection "i"
II 3 G Ex ic nA IIC T5 Gc – for 1794-AENTR only
II 3 G Ex ic nA IIC T4 Gc – for 1794-AENTRXT only
TÜV TÜV Certified for Functional Safety:
Capable of SIL 2
EtherNet/IP ODVA conformance tested to EtherNet/IP specifications
KC Korean Registration of Broadcasting and Communications
Equipment, compliant with:
Article 58-2 of Radio Waves Act, Clause 3
(1)
See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates, and other
certification details.
WARNING
For Class I Division 2 applications, use only Class I Division 2 listed or
recognized accessories and modules approved for use within the
1794 platform.
45826
1794-AENTR
shown
Millimeters
(Inches)
80.4
(3.16)
87.4
(3.44)
94
(3.70)
1794-AENTR, 1794-AENTRXT
87.4 H x 94W x 92D
(344H x 3.7W x 3.6D)
50
(1.96)
30.4
(1.19)
Zobrazit stránku 5