ArmorBlock 2 Input/2 Output Module
Publication 1792-5.5 – October 1996
Bit
07 06 05 04 03 02 01 00
Produces IS Reserved OF1 OF0 I1 I0
Consumes Reserved O1 O0
Where: I = Input
IS = Sensor source voltage fault
O = Output
OF = Output fault
Word Bit Description
Produces
00–01 Input bits – bit 00 corresponds to input 0, bit 01 to input 1. When the
bit is set (1), the input is on.
02–03 Output fault bits – Shows fault status of each output. OS0
corresponds to output 0, and OS1 corresponds to output 1. When
the bit is set (1), the output is faulted.
04–06 Reserved
07 Sensor source voltage fault bit – this bit is set (1) when the sensor
source voltage is faulted.
Consumes
00–01 Output bits – Bit 00 corresponds to output 0, bit 01 corresponds to
output 1. 0 = output off; 1 = output on
02–07 Reserved
Configure
Y
our Armor Module Offline Using the
DeviceNet Manager Configuration Tool
To configure your ArmorBlock module offline:
• add the device to the network
• set the parameters for the device
• save the parameters to a file
Note: You cannot actually configure your device offline. You can set
and save the parameters to a file for downloading to the device when
you go online.