Rockwell Automation Publication 1788-UM057B-EN-P - September 2014 21
Chapter 2
Set Up in the Studio 5000
Logix Designer Application
Add the 1788-EN2FFR Linking
Device to the I/O Tree
The 1788-EN2FFR linking device must be added to the I/O tree of the Logix
controller. The linking device must be added to an Ethernet bridge, such as an
Allen-Bradley® 1756-EN2T or 1756-EN2TR module.
Follow these steps to add the linking device to the I/O tree of the Logix
controller. This example uses the 1756-EN2TR module.
1. Right-click the Ethernet bridge and choose New Module.
2. Select the linking device that you want to add to the Ethernet bridge.
3. Click the General tab and set the name, description, and IP address.