18 ControlNet-to-DeviceNet Linking Device
Publication
1788-IN052D-EN-P - February 2007
2. Wrap the end of the cable with 38 mm (1.5 in.) of shrink wrap,
covering part of the exposed conductors and part of the trunk
line insulation.
3. Strip 8.1 mm (0.32 in.) of the insulation from the end of each
of the colored insulated conductors.
4. Insert each colored conductor into the matching color-coded
terminal cavity of the open-style connector.
5. If the CN2DN device is the first or last node on the DeviceNet
network, insert an end of a 121resistor into the blue and
white terminal cavities of the DeviceNet port connector.
Jacket
38 mm
(1.5 in.)
Shrink Wrap
41841
Shrink Wrap
Jacket
8.1 mm
(0.32 in.)
41842