4–15Configuring the Module
Publication 1771ĆUM127B-EN-P - December 2002
RTD Type
This field lets you select the type of sensor connected to a 650 ohm
input channel. This field must be 0 for all other channel types.
Sensor Type Binary Value
Decimal 10 09 08
Octal 12 11 10
Resistance 0 0 0
100 Ohm Pt. European Std. 0 0 1
100 Ohm Pt. U.S. Std. 0 1 0
10 Ohm Copper 0 1 1
120 Ohm Nickel 1 0 0
10 Ohm Offset
This field lets you compensate for a small offset error in a 10 ohm
copper RTD. Values can range from -0.99 to +0.99 ohms in units of
0.01 ohms.
For example, if the resistance of a copper RTD used with this
channel was 9.74 ohms at 25
o
C, you would enter -0.26 in this field.
The configuration block for a block transfer write consists of:
module configuration header
output channel data (if applicable)
output channel programming (if applicable)
input channel programming (if applicable)
Block Transfer Write Configuration Data Header
The configuration data header consists of information required for
the processor to properly identify the type of information it will be
receiving.
Module Configuration Data Header
Word/Dec. Bit
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Word/Octal Bit
17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00
0
BTW word type Constant Number of outputs Constant
0
1 0 0 0 1 0 0 0 0 0 1 0 0 0 0 0
Configuration Block for a
Block Transfer Write
Zobrazit stránku 54