Publication 1771Ć6.5.116 - June 1996
" 
!   ! "!  #$
 !!
Source Ground
1
. Unused channels must have their + and Ć inputs jumpered
together and tied to module common to reduce noise.
1771ĆWG
Field Wiring Arm
10949ĆI

The 1771ĆIFF module does not supply loop power for the input device. The user must supply
loop power for loopĆpowered input devices.
+
-
Channel 1+
Channel
Channel 2+
Channel
Channel 3+
Channel
Channel 4+
Channel
Channel 5+
Channel
Channel 6+
Channel
Channel 7+
Channel
Channel 8+
Channel
Module Common
Not used
Not used
Not used
Module Common
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
Configuring the module for differential inputs does not provide isolation.
The sensor cable must be shielded. The shield must:
extend the length of the cable, but be connected only at the 1771
I/O chassis
extend up to the point of termination
!! The shield should extend to the termination point,
exposing just enough cable to adequately terminate the
inner conductors. Use heat shrink or another suitable
insulation where the wire exits the cable jacket.
2
Tie power supply grounds together to
minimize ground loops.
! Refer to transmitter manufacturers
specifications for power supply connections.
+
Power
Supply
2ĆWire
Transmitter
Power
Supply
2ĆWire
Transmitter
-