14 Compact I/O Analog Output Module
Publication 1769-IN087A-EN-P - August 2009
Wire Size and Terminal Screw Torque
Each terminal accepts two wires with the following restrictions.
Configure the 1769-OF4 Module
The following I/O memory mapping lets you configure the 1769-OF4 module.
Output Data File
For each module, slot x, words 0…3 in the output data file contain the control
program’s directed state of the module’s analog output channels. Word 4 contains
the cancel output-channel-clamp alarm control bits.
The bits are defined as follows:
• SGN = Sign bit in 2’s complement format.
• NU = Not used. Bit must be set to 0.
• CHOx = Cancel High Clamp Alarm Latch for Output x: Allows each output
high-clamp-alarm latch to be individually cancelled. NOTE: Cancel = 1.
• CLOx = Cancel Low Clamp Alarm Latch for Output x: Allows each output
low-clamp-alarm-latch to be individually cancelled. NOTE: Cancel = 1.
Wire Type Wire Size Terminal Screw
Torque
Retaining Screw
Torque
Solid Cu-90 °C (194 °F) 14…22 AWG
(2.08…0.33 mm
2
)
0.68 N•m (6 lb•in) 0.46 N•m (4.1 lb•in)
Stranded Cu-90 °C (194 °F) 16…22 AWG
(1.31…0.33 mm
2
)
0.68 N•m (6 lb•in) 0.46 N•m (4.1 lb•in)
Word/Bit 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Word 0 SGN Analog Output Data Channel 0
Word 1 SGN Analog Output Data Channel 1
Word 2 SGN Analog Output Data Channel 2
Word 3 SGN Analog Output Data Channel 3
Word 4 NU NUNUNUNUNUNUNUCL
O3
CH
O3
CL
O2
CH
O2
CL
O1
CH
O1
CL
O0
CH
O0